ViM BATE-R Instruction Manual

ViM BATE-R Instruction Manual

Circular electrical heater with built-in stand-alone control
Hide thumbs Also See for BATE-R:

Advertisement

Quick Links

INSTRUCTION MANUAL
INSTALLATION | WIRING | COMMISSIONING | MAINTENANCE |
I S O 9 0 0 1
ISO 14001
Q u a l i t é
Environnement
AFNOR CERTIFICATION
AFNOR CERTIFICATION
BATE-R
Circular electrical heater with built-in stand-alone control
NT00000591-BATE-R-AN-191114

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BATE-R and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ViM BATE-R

  • Page 1 INSTRUCTION MANUAL INSTALLATION | WIRING | COMMISSIONING | MAINTENANCE | I S O 9 0 0 1 ISO 14001 Q u a l i t é Environnement AFNOR CERTIFICATION AFNOR CERTIFICATION BATE-R Circular electrical heater with built-in stand-alone control NT00000591-BATE-R-AN-191114...
  • Page 2: Table Of Contents

    Assembly ..........................5 ELECTRICAL CONNECTION ......................6 BATE-R Single-phase + duct temperature sensor ..............6 BATE-R Single-phase + ambient temperature sensor and supply air temperature limitation sensor ............................8 BATE-R Three-phase + duct temperature sensor ..............10 BATE-R Three-phase + ambient temperature sensor and supply air temperature limitation sensor .............................
  • Page 3: General Information

    In any event, the seller is not responsible for equipment that has been modified or repaired even partially. 3/16 NT00000591-BATE-R-AN-191114...
  • Page 4: Range / Product Presentation

    Single-phase 230V 4 000 2850 276 376 470 50,0 BATE R 400 3 000W Single-phase 230V 3 000 13,0 4 600 21,7 276 376 470 50,0 Single-phase 230V 5 000 10,2 4 600 BATE R 400 5 000W 4/16 NT00000591-BATE-R-AN-191114...
  • Page 5: Assembly

    Attention, the control circuit is not galvanically isolated from the device’s power circuit. Electrical wires and cables • Max wire diameter for control connections: up to 4mm • Max cable diameter for power supply: 10mm 16mm ≤ 4,5kW ˃ 4,5kW Mono 230V ≤ 15kW ˃ 15kW Tri 400V 5/16 NT00000591-BATE-R-AN-191114...
  • Page 6: Electrical Connection

    ELECTRICAL CONNECTION 4.1 BATE-R Single-phase + duct temperature sensor Supply air temperature control with DIP switch in position “1”. Temperature setting on TR5K unit. BATE-R Single-phase < 4kW - Duct temperature control 230Vac 230Vac 50Hz 50Hz Heater post-ventilation On/O delay...
  • Page 7 BATE-R Single-phase ≥ 4kW - Duct temperature control 230Vac 230Vac 50Hz 50Hz Heater post-ventilation On/O delay MCR1 BATE-R 2 sensors (ambience control) 1 sensor (supply air control) 0... 10 SetP Trég Gnd Tamb 16 15 18 KM10 air ow On/O controller Trég...
  • Page 8: Bate-R Single-Phase + Ambient Temperature Sensor And Supply Air Temperature Limitation Sensor

    4.2 BATE-R Single-phase + ambient temperature sensor and supply air temperature limitation sensor Ambient temperature control and supply air temperature limitation with DIP switch in “On” position. Tem- perature setting on TR5K unit. BATE-R Mono < 4kW - Ambient temperature control, duct temperature limitation 230Vac 230Vac 50Hz...
  • Page 9 BATE-R Mono ≥ 4kW - Ambient temperature control, duct temperature limitation 230Vac 230Vac 50Hz 50Hz Heater post-ventilation On/O delay BATE-R MCR1 ≥4kW 2 sensors (ambience control) 1 sensor (supply air control) limitations : mini +15°C maxi +40°C SetP 0... 10 Trég Gnd...
  • Page 10: Bate-R Three-Phase + Duct Temperature Sensor

    4.3 BATE-R Three-phase + duct temperature sensor Supply air temperature control with DIP switch in position “1”. Temperature setting on TR5K unit. BATE-R Three-phase < 18kW - Duct temperature control 400Vac 230Vac 50Hz 50Hz Heater post-ventilation On/O delay MCR1 BATE-R <18kW...
  • Page 11 BATE-R Three-phase ≥ 18kW - Duct temperature control 400Vac 230Vac 50Hz 50Hz Heater post-ventilation On/O delay MCR1 BATE-R ≥18kW 2 sensors (ambience control) 1 sensor (supply air control) SetP 0... 10 Trég Gnd Tamb 16 15 18 KM10 On/O air ow controller Trég...
  • Page 12: Bate-R Three-Phase + Ambient Temperature Sensor And Supply Air Temperature Limitation Sensor

    4.4 BATE-R Three-phase + ambient temperature sensor and supply air temperature limitation sensor Ambient temperature control and supply air temperature limitation with DIP switch in “On” position. Tem- perature setting on TR5K unit. BATE-R Mono < 18kW - Ambient temperature control, duct temperature limitation. 400Vac 230Vac 50Hz...
  • Page 13 BATE-R Mono ≥ 18kW - Ambient temperature control, duct temperature limitation. 230Vac 400Vac 50Hz 50Hz Heater post-ventilation On/O delay MCR1 BATE-R ≥18kW 2 sensors (ambience control) 1 sensor (supply air control) limitations : mini +15°C maxi +40°C SetP 0... 10 Trég Gnd...
  • Page 14: Commissioning And Maintenance

    If the manual reset safety thermostat is activated, take the following measures: Cut off the power supply. Carefully identify why the safety thermostat was ac- tivated. Once the error has been corrected, press the man- ual safety thermostat button on the coil unit cover. 14/16 NT00000591-BATE-R-AN-191114...
  • Page 15: Maintenance

    It is strictly prohibited to burn, bury or illegally dispose of them. 6.2 Processing of Professional WEEE This product must not be disposed of or processed with household waste but must be dropped off at an appropriate collection point for waste electrical and electronic equipment (WEEE). 15/16 NT00000591-BATE-R-AN-191114...
  • Page 16 Les prés de Mégy Sud – SOUDAN CS 60120 - 79401 ST MAIXENT L’ECOLE CEDEX Tel.: 05 49 06 60 38 or 05 49 06 60 25 – Fax: 05 49 06 60 36 sav@vim.fr - www.vim.fr 16/16 NT00000591-BATE-R-AN-191114...