Rectangular electrical heater, power control fitted (16 pages)
Summary of Contents for ViM BATE-R010
Page 1
INSTALLATION | WIRING | COMMISSIONING | MAINTENANCE | I S O 9 0 0 1 ISO 14001 Q u a l i t é Environnement AFNOR CERTIFICATION AFNOR CERTIFICATION BATE-R010 Circular electrical heater with built-in control for external 0-10V signal NT00000592-BATE-R-010-AN-191114...
1.2 Safety instructions Put on appropriate PPE (Personal Protective Equipment) before any work, If work has to be carried out on the device, cut off the power supply on the main circuit breaker and make sure that nobody can accidentally turn it back on, Before operating the equipment, check the following points: • Make sure that the device does not contain any foreign bodies, •...
• Max cable diameter for power supply: 10mm 16mm ≤ 4,5kW ˃ 4,5kW Mono 230V ≤ 15kW ˃ 15kW Tri 400V ELECTRICAL CONNECTION 4.1 BATE-R010 Single-phase - Power < 4kW BATE-R010 <4kW 1 phase power supply 230V 50Hz air ow according to NF C 15-100 standard controller 50°C auto θ...
4.2 BATE-R010 Single-phase - Power ≥ 4kW BATE-R010 1 phase power supply ≥4kW 230V 50Hz air ow according to NF C 15-100 standard controller 50°C auto θ reset Safety thermostat manual 100°C reset θ Command signal 0...10VDC Equipment Included Optional...
4.4 BATE-R010 Three-phase - Power ≥ 18kW BATE R010 3 phases power supply 400V 50Hz air ow according to NF C 15-100 standard controller 50°C auto θ reset Safety thermostat 100°C manual θ reset Command signal 0...10Vcc In any case, it must not be possible to shut off the fan without the heater shutting off beforehand (MCR1- type post-ventilation delay if necessary) or at the same time (to be avoided),...