6. Configuration

The preset switch-off time of 4 sec can be changed. It is to be agreed
upon with the local expert.
Vorsicht
Setting the switch-off time:
• Open SMHC2. To do this, release the fixing screws (3) and pull the hood (7) off the
holder (5) –with the device disconnected from the power supply (see chap. 5.1)
• After unlatching the back plate, pull the circiut board out of the hood (7). At the circuit
board you find a two-pole DIP switch on the right side below the LEDs (see diagram).
The switch off time can be adjusted as shown in the table:
DIP-switch
Switch-off time
1
2
on
on
off
on
on
off
off
off

7. Technical data

7.1 Device data - controller

Production according to:
Certificate No.
EC-Type-Examination PED:
CE ID No.:
Safety Integrity level:
Applied Standards:
additional technical standards:
22
4 s
8 s
12 s
16 s
EU-Directive 2014/68/EU, Annex III
Modules B+D (Category IV)
01 202 931-B-16-0021
0035
SIL3
DIN EN 12952-11: 2007, DIN EN 12953- 9: 2007,
DIN EN 61508-1/ -2/ -3: 2010,
DIN EN 61326-1: 2006, DIN EN 61326-3-2: 2006
DIN EN 60730-1: 2014-07
Water Level 100 (Wasserstand 100) edition date
02.2010; ASME Boiler