8. RESET AND DEFAULT SETTINGS

8.1

General system reset

To reset PMW press and hold the 4 buttons simultaneously for 2 Sec. This operation does not delete settings memorised by the
user.
8.2

Default settings

The inverter leaves the factory with a series of pre-set parameters, which can be modified according to user requirements. Each
modification to settings is automatically saved in the memory, while the user, when required, can always restore the default
conditions (see Ripristino delle impostazioni di fabbrica par. 8.3).
8.3

Restoring default settings

To restore the default settings, switch off the inverter, wait for complete shutdown of the fans and display, then press and hold
buttons "SET" and "+" and power up the unit; only release the two buttons when the text "EE" is displayed.
In this case the default settings are restored (writing and reading on EEPROM of the default settings saved permanently on the
FLASH memory).
After setting all parameters, the inverter resumes normal operation.
After restoring default settings, all system parameters should be reconfigured (current, gain, minimum frequency, setpoint
pressure etc.) as per the initial installation procedure
Identifier
LA
Language
SP
Setpoint pressure [bar]
P1
Setpoint P1 [bar]
P2
Setpoint P2 [bar]
P3
Setpoint P3 [bar]
P4
Setpoint P4 [bar]
FP
Test frequency in manual mode
RC
Rated current of electric pump [A
RT
Direction of rotation
FN
Rated frequency [Hz]
OD
Type of system
RP
Pressure drop for restart [bar]
AD
Address
PR
Pressure sensor
MS
Measurement system
FI
Flow sensor
FD
Pipeline diameter [inch]
FK
K-factor [pulse/l]
FZ
Setting zero flow frequency
FT
Minimum shutdown flow [ l/min]
SO
Dry running factor
MP
Minimum pressure pump stop [bar]
TB
Delay for water failure block [s]
T1
Shutdown delay [s]
T2
Shutdown delay [s]
GP
Proportional gain coefficient
GI
Integral gain coefficient
FS
Maximum rotation frequency [Hz]
FL
Minimum rotation frequency [Hz]
Default settings
Description
ENGLISH
.
PWM 203
PWM 407
202 - 201
405 - 404
Value
ITA
ITA
3,0
3,0
2,0
2,0
2,5
2,5
3,5
3,5
4,0
4,0
40,0
40,0
0,0
0,0
0 (UVW)
0 (UVW)
50,0
50,0
1 ( Rigid )
1 ( Rigid )
0,5
0,5
0 (Auto)
0 (Auto)
1
1
(501 R 25 bar)
(501 R 25 bar)
0 (International )
0 (International)
0 ( Absent )
0 ( Absent )
2
2
24,40
24,40
0
0
5
5
22
22
0,0
0,0
10
10
2
2
10
10
0,6
0,6
1,2
1,2
50,0
50,0
0,0
0,0
115
PWM 420 415 -
Installation
410
note
ITA
3,0
2,0
2,5
3,5
4,0
40,0
0,0
0 (UVW)
50,0
1 ( Rigid )
0,5
0 (Auto)
1
(501 R 25 bar)
0
( International )
0 ( Absent )
2
24,40
0
5
22
0,0
10
2
10
0,6
1,2
50,0
0,0