14. Performance curves

14.1 Guide to performance curves

Each pump setting has its own performance curve.
A power curve, P1, belongs to each performance curve. The power
curve shows the pump power consumption in watt at a given
performance curve.

14.2 Curve conditions

The guidelines below apply to the performance curves:
Test liquid: airless water.
The curves apply to a density of 983.2 kg/m
temperature of 20 °C.
All curves show average values and must not be used as
guarantee curves. If a specific minimum performance is
required, individual measurements must be made.
The curves apply to a kinematic viscosity of 0.474 mm
(0.474 cSt).
The conversion between head H [m] and pressure p [kPa] has
been made for water with a density of 1000 kg/m
with other densities, for example hot water, the outlet pressure
is proportional to the density.
Curves are obtained according to EN 16297.
It is not obligatory to show P
the yearly expectable average power consumption.
Maximum curves are limited by speed and power
20
3
and a liquid
2
/s
3
. For liquids
, but it gives an indication on
L,Avg