Cooling Operation - Fujitsu ASU9RL Service Instruction

Hide thumbs Also See for ASU9RL:
Table of Contents

Advertisement

1. COOLING OPERATION

1-1 COOLING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is
frequency will attain to maximum performance.
* If the room temperature is
stopped.
* When the room temperature is between
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Figure 1 based on the
fan speed mode and the outdoor temperature.
( Table 1 : Compressor Frequency Range )
ASU9RL
ASU12RL
( Fig. 1 : Limit of Maximum Frequency based on Outdoor Temperature )
Outside air
temperature
A zone
93°F
(34°C)
B zone
86°F
(30°C)
C zone
66°F
(19°C)
D zone
50°F
(10°C)
E zone
32°F
(0°C)
F zone
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency
4°F(2°C)
higher than a set temperature, the compressor operation
5°F(2.5°C)
lower than a set temperature, the compressor will be
+4°F(+2°C)
minimum
maximum
frequency
frequency
22Hz
76Hz
18Hz
80Hz
Outside air
temperature
97°F
9RL
(36°C)
90°F
(32°C)
70°F
(21°C)
12RL
54°F
(12°C)
36°F
(2°C)
05-01
to
-5°F(-2.5°C)
of the setting temperature,
maximum
frequency
79Hz
96Hz
Hi
Me
A zone
79Hz
61Hz
B zone
79Hz
61Hz
C zone
79Hz
61Hz
D zone
52Hz
43Hz
E zone
64Hz
55Hz
F zone
64Hz
55Hz
A zone
96Hz
61Hz
B zone
96Hz
61Hz
C zone
96Hz
61Hz
D zone
57Hz
42Hz
E zone
57Hz
42Hz
F zone
57Hz
42Hz
to Maximum Frequency .
Lo
Quiet
52Hz
37Hz
52Hz
37Hz
52Hz
37Hz
37Hz
28Hz
49Hz
36Hz
49Hz
36Hz
51Hz
33Hz
51Hz
33Hz
51Hz
33Hz
36Hz
27Hz
36Hz
27Hz
36Hz
27Hz