2. HEATING OPERATION

2-1 HEATING CAPACITY CONTROL
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
* If the room temperature is lower by
frequency will attain to maximum performance.
* If the room temperature is higher
stopped.
* When the room temperature is between
the compressor frequency is controlled within the range shown in Table2.
However, the maximum frequency is limited in the range shown in Figure 2 based on the
fan speed mode and the outdoor temperature.
( Table 2 : Compressor Frequency Range )
ASU9RL
ASU12RL
( Fig.2 : Limit of Maximum Frequency based on Outdoor Temperature )
Outside air
temperature
C zone
63°F
(17°C)
B zone
53°F
(12°C)
A zone
41°F
(5°C)
AA zone
* The room temperature is controlled
after starting the operation.
After 60 minutes, it is controlled based on the normal setting temperature.
6°F(3°C)
5°F(2.5°C)
+5°F(+2.5°C)
minimum
maximum
frequency
frequency
22Hz
99Hz
18Hz
130Hz
Outside air
temperature
66°F
9RL
(19°C)
57°F
(14°C)
12RL
45°F
(7°C)
4°F(2°C)
05-02
than a set temperature, the compressor operation
than a set temperatire, the compressor will be
to
-6°F(-3°C)
of the setting temperature,
Hi
Me+
AA zone
99Hz
99Hz
A zone
99Hz
99Hz
B zone
99Hz
99Hz
C zone
99Hz
99Hz
AA zone
130Hz
130Hz
A zone
130Hz
130Hz
B zone
130Hz
130Hz
130Hz
130Hz
C zone
higher than the setting temperature for 60 minutes
Me
Lo
Quiet
90Hz
79Hz
70Hz
90Hz
79Hz
70Hz
90Hz
79Hz
58Hz
90Hz
79Hz
49Hz
105Hz
80Hz
64Hz
105Hz
80Hz
64Hz
105Hz
80Hz
51Hz
105Hz
80Hz
42Hz