1 Placement of cabinet

• Measures of Cabinet 42 U: Width: 600mm, depth:
1000mm and height: 2100mm.
• Measures of Cabinet 24 U: Width: 600mm, depth:
1000mm and height: 1300mm.
• Leave 5 cm at the back of the cabinet to ensure free
airflow.
• EnergyHub XL is pushed from the front into the cabinet
and it is therefore recommended to have at least 1
meter of free space up front to facilitate installation.
• Make sure to have access to at least one of the sides
or the back of the cabinet during installation to facilitate
contacting
• The side walls of the cabinet are removable.
• Temperature: -25 – 55
• Relative humidity: 0-95%
• The room where the inverter is placed should be well ventilated. The heat development
can be up to 2% of the maximum effect. A fully fitted cabinet with 5x28 kW can generate
2.8 kW of heat at 2% loss.