6. Space required for unit installation and operation

1 In case of single installation
Secure enough space around the unit as shown in the figure.
If the wall height exceeds the height limit, widen the space labeled "L" and "W" by the amount that exceeds the limit (labeled <h> in the figure).
[Fig. 6.0.1]
(1) Walls are lower than the height limit.
500 [19-11/16]
W
L
W
450 [17-23/32]
Condition
Minimum space behind the unit
Minimum space on both sides of the unit
(2) If the wall height (H) of the front, rear or side exceeds the wall height restriction
h
h
500
W
[19-11/16]
L
W
450 [17-23/32] + h
Condition
Minimum space behind the unit
Minimum space on both sides of the unit
(3) If there are obstacles at the upper part of the unit
240 [9-15/32]
45°
50 [1-31/32]
6
L
W
100 [3-15/16]
50 [1-31/32]
300 [11-13/16]
15 [19/32]
W
W
450 [17-23/32] + h
L
W
100 [3-15/16] + h
50 [1-31/32] + h
300 [11-13/16] + h
15 [19/32] + h
1000 [39-3/8]
Air deflector grills
(field supplied)
h
h
500 [19-11/16]
h
W
L
W
450 [17-23/32] + h
h
500 [19-11/16]
L
(Unit : mm [in.])