Mitsubishi Electric City Multi PUHY-P72TKMU-A Installation Manual page 11

Air-conditioners for building application inverter y-series
Hide thumbs Also See for City Multi PUHY-P72TKMU-A:
Table of Contents

Advertisement

Available languages

Available languages

A
Unit combination
Outdoor model
Unit 1
Unit 2
Unit 3
P72T/YKMU
-
-
-
P96T/YKMU
-
-
-
P120T/YKMU
-
-
-
P144T/YKMU
-
-
-
P144YSKMU
P72
P72
P168T/YSKMU
P96
P72
-
P192T/YSKMU
P120
P72
-
P216T/YSKMU
P120
P96
-
P240T/YSKMU
P120
P120
-
P264T/YSKMU
P120
P72
P72
P288T/YSKMU
P120
P96
P72
P312T/YSKMU
P120
P120
P72
P336T/YSKMU
P120
P120
P96
P360T/YSKMU
P120
P120
P120
*1 ø12.7 for over 90m [295 ft]
*2 ø12.7 for over 40m [131 ft]
*3 The pipe sizes listed in columns A1 to A3 in this table correspond to the sizes for the models listed in the unit 1, 2, and 3 columns. When the order of the models for
unit 1, 2, and 3 change, make sure to use the appropriate pipe size.
*4 B If the piping length after the first joint exceeds 40 m (≤ 90 m), use the one size larger liquid pipe for the indoor unit.
*5 C When the height difference between the indoor units is 15 m or greater (≤ 30 m), use the one size larger liquid pipe for the indoor unit (lower side).
B,C,D
Total capacity of indoor units
~ 54
55 ~ 72
73 ~ 108
109 ~ 144
145 ~ 240
241 ~ 308
309 ~
a,b,c,d,e
Model number
06, 08, 12, 15, 18
24, 27, 30, 36, 48, 54
72
96
A
A1
*3
Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Liquid pipe Gas pipe
ø9.52 [3/8] ø22.2 [7/8]
-
*1
ø9.52 [3/8] ø22.2 [7/8]
-
*2
ø9.52 [3/8] ø28.58 [1-1/8]
-
ø12.7 [1/2] ø28.58 [1-1/8]
-
ø12.7 [1/2] ø28.58 [1-1/8] ø9.52 [3/8] ø22.2 [7/8] ø9.52 [3/8] ø22.2 [7/8]
ø15.88 [5/8] ø28.58 [1-1/8] ø9.52 [3/8] ø22.2 [7/8] ø9.52 [3/8] ø22.2 [7/8]
ø15.88 [5/8] ø28.58 [1-1/8] ø12.7 [1/2] ø28.58 [1-1/8] ø9.52 [3/8] ø22.2 [7/8]
ø15.88 [5/8] ø28.58 [1-1/8] ø12.7 [1/2] ø28.58 [1-1/8] ø9.52 [3/8] ø22.2 [7/8]
ø15.88 [5/8] ø28.58 [1-1/8] ø12.7 [1/2] ø28.58 [1-1/8] ø12.7 [1/2] ø28.58 [1-1/8]
ø19.05 [3/4] ø34.93 [1-3/8] ø12.7 [1/2] ø28.58 [1-1/8] ø9.52 [3/8] ø22.2 [7/8] ø9.52 [3/8] ø22.2 [7/8] ø19.05 [3/4] ø34.93 [1-3/8]
ø19.05 [3/4] ø34.93 [1-3/8] ø12.7 [1/2] ø28.58 [1-1/8] ø9.52 [3/8] ø22.2 [7/8] ø9.52 [3/8] ø22.2 [7/8] ø19.05 [3/4] ø34.93 [1-3/8]
ø19.05 [3/4] ø34.93 [1-3/8] ø12.7 [1/2] ø28.58 [1-1/8] ø12.7 [1/2] ø28.58 [1-1/8] ø9.52 [3/8] ø22.2 [7/8] ø19.05 [3/4] ø34.93 [1-3/8]
ø19.05 [3/4] ø41.28 [1-5/8] ø12.7 [1/2] ø28.58 [1-1/8] ø12.7 [1/2] ø28.58 [1-1/8] ø9.52 [3/8] ø22.2 [7/8] ø19.05 [3/4] ø34.93 [1-3/8]
ø19.05 [3/4] ø41.28 [1-5/8] ø12.7 [1/2] ø28.58 [1-1/8] ø12.7 [1/2] ø28.58 [1-1/8] ø12.7 [1/2] ø28.58 [1-1/8] ø19.05 [3/4] ø34.93 [1-3/8]
(Unit: mm [in])
Liquid pipe
Gas pipe
ø9.52 [3/8]
ø15.88 [5/8]
ø9.52 [3/8]
ø19.05 [3/4]
ø9.52 [3/8]
ø22.2 [7/8]
ø12.7 [1/2]
ø28.58 [1-1/8]
ø15.88 [5/8]
ø28.58 [1-1/8]
ø19.05 [3/4]
ø34.93 [1-3/8]
ø19.05 [3/4]
ø41.28 [1-5/8]
(Unit: mm [in])
Liquid pipe
Gas pipe
ø6.35 [1/4]
ø12.7 [1/2]
ø9.52 [3/8]
ø15.88 [5/8]
ø9.52 [3/8]
ø19.05 [3/4]
ø9.52 [3/8]
ø22.2 [7/8]
A2
*3
A3
*3
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Downstream unit model total
~ 72
73 ~ 144
145 ~ 240
The 1st branch of P144 ~ P240
241 ~
The 1st branch of P264 ~ P360
4-Branch header
8-Branch header
(Downstream indoor
(Downstream indoor
unit model total 72)
unit model total 144)
CMY-Y104C-G
CMY-Y108C-G
Outdoor model
P144YSKMU, P192 ~ 240T/YSKMU
P264 ~ P360T/YSKMU
*1 P144 has YSKMU model only.
(Unit: mm [in])
A4
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Joint
CMY-Y102SS-G2
CMY-Y102LS-G2
CMY-Y202S-G2
CMY-Y302S-G2
10-Branch header
(Downstream indoor
unit model total 240)
CMY-Y1010C-G
Outdoor Twinning Kit
CMY-Y100CBK3
CMY-Y300CBK2
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

City multi puhy-p72tkmu-a-bsCity multi puhy-p96tkmu-aCity multi puhy-p96tkmu-a-bsCity multi puhy-p120tkmu-aCity multi puhy-p120tkmu-a-bsCity multi puhy-p144tkmu-a ... Show all

Table of Contents