Setting Value - Daiichi Electronics FINE Series Instruction Manual

Plug-in transducer alarm setter
Table of Contents

Advertisement

5.5 Setting value

Contents
1
Unit display
2
Minimum value scaling
3
Maximum value scaling
4
Output mode
5
Operation value
AL1
6
Dead band
7
Excitation mode
8
Contact delay time (CD)
9
Output mode
10
Operation value
AL2
11
Dead band
12
Excitation mode
13
Contact delay time (CD)
14
Output mode
15
Operation value
AL3
16
Dead band
17
Excitation mode
18
Contact delay time (CD)
19
Output mode
20
Operation value
AL4
21
Dead band
22
Excitation mode
23
Contact delay time (CD)
24 Starting delay time (SD)
25 Bias point calibration
26 Span point calibration
27 Average number
28 Pre-alarm
< Notes of setting >
・The decimal point position change of scaling is made by the minimum value scaling.
If the decimal point position is changed, the decimal point position of maximum value scaling and operation
values 1 to 4 will also change. If the decimal point position is changed, please be sure to check the set
value of a maximum value scaling and an operation value.
・When changing the scaling, set the operation values 1 to 4 within the measurement display range (see below).
Even if the output mode is set to OFF, keep it within the measurement display range.
・An operation value can be set up in -25 to +125% of the measurement display range (minimum value scaling
to maximum value scaling).
(Example) Input 4 to 20mA,
Operation value -25.0,
Output mode is "Low" setting.
・After setting change, in case a set value combination error occurs, it becomes a setting error display.
Please push the
Default setting value
Mark
2 contact
outputs
UNIT
MIN
MAX
ALMD1
High
COMP1
70.0
D.B.1
EXMD1
C.D.1
ALMD2
Low
COMP2
30.0
D.B.2
EXMD2
C.D.2
ALMD3
COMP3
D.B.3
EXMD3
C.D.3
ALMD4
COMP4
D.B.4
EXMD4
C.D.4
S.D.
CBIAS
CSPAN
AVE
PREAL
125%
100%
-25%
key and set up the right set value (in set value change mode).
3 contact
4 contact
outputs
outputs
0.0
100.0
High
High
80.0
80.0
3.0
0N
0
High
High
70.0
70.0
3.0
0N
0
Low
Low
30.0
30.0
3.0
ON
0
Low
20.0
3.0
ON
0
5
0.00
0.00
1
OFF
24mA
20mA
50%
12mA
Becomes the L detected at the input 0mA,
can also be used as a disconnection
0%
4mA
detection.
0mA
17
Setting range
% , m, ℃, m
/h, ppm, pH, TPm, ×10kg,
Ω,kW,No unit
-9999 to 9999
-9.99 to 99.99
-99.9 to 999.9
0.000 to 9.999
High:H operation,Low:L operation,
OFF :With no operation
Measurement display range -25 to
+125% (Real scale)
0.5 to 50.0%
ON:Excitation,OFF:Non-excitation
0 to 180s
High:H operation,Low:L operation,
OFF :With no operation
Measurement display range -25 to
+125% (Real scale)
0.5 to 50.0%
ON:Excitation,OFF:Non-excitation
0 to 180s
High:H operation,Low:L operation,
OFF :With no operation
Measurement display range -25 to
+125% (Real scale)
0.5 to 50.0%
ON:Excitation,OFF:Non-excitation
0 to 180s
High:H operation,Low:L operation,
OFF :With no operation
Measurement display range -25 to
+125% (Real scale)
0.5 to 50.0%
ON:Excitation,OFF:Non-excitation
0 to 180s
1 to 180s
-9.99 to 9.99% (% of input span)
-9.99 to 9.99% (% of input span)
1,4,8,16,32
ON:Pre-alarm ON, OFF:Pre-alarm OFF
FSDLC-220-047