Occupant sensors

Advertisement

Quick Links

Sensors
Infrared Ceiling Mount Sensor
Models Available
Cat. No.
ULOS-CIR-450-WH
ULOS-CIR-1500-WH
Self-Adaptive Feature
The ULOS-CIR Series ceiling-mount occupant sensors provides reliable detection with high error immunity.
The internal microprocessor analyzes the information from the PIR technology and determines the optimum
setting to use in order to properly cover the space.
S P ECI FI CA TIO N S UB MI TT AL
®
Job Name:
Job Number:
ULOS-CIR Series
The ULOS-CIR Series ceiling-mount passive infrared
sensors can integrate into Lutron systems or function
as stand-alone controls using a Lutron power pack. The
sensor uses a small semiconductor heat detector that
resides behind a multi-zone optical lens. The sensor's
detector is sensitive to the heat emitted by the human
body. In order to trigger the sensor, the source of heat
must move from one range of detection to another. Non-
moving hot objects will not cause the lights to turn on.
Features
• Intelligent, continually adapting passive infrared
(PIR) sensor
• Passive infrared sensing
• Reliable motion detection with high error immunity
• Snap-locks to ceiling-mounted cover plate
• Non-Volatile Memory: settings saved in protected
memory are not lost during power outages
• 450 to 1500 sq ft (42 to 140 m
mounted on an 8 - 12 ft (2.4 - 3.7 m) ceiling
• Affords choice of turning lights off or dimming to a preset
level in the unoccupied state when integrated with a
Lutron system.
• Assembled in the USA.
Color
Coverage
White
450 sq ft (42 m
White
1500 sq ft (140 m
Model Numbers:
Occupant Sensors
) coverage when
2
Field of View
2
)
360°
)
360°
2
369656b 1 05.04.12
Page

Advertisement

loading

Summary of Contents for Lutron Electronics ULOS-CIR Series

  • Page 1 360° Self-Adaptive Feature The ULOS-CIR Series ceiling-mount occupant sensors provides reliable detection with high error immunity. The internal microprocessor analyzes the information from the PIR technology and determines the optimum setting to use in order to properly cover the space.
  • Page 2: Specifications

    ULOS-CIR Series Occupant Sensors Sensors 369656b 2 05.04.12 Specifications Timer Adjustment Power • Automatic mode: Continually adapting • Operating voltage: 20 - 24 V sensor automatically adjusts settings to PELV (Class 2: USA) low- the space voltage • Manual mode: 8 to 30 minutes •...
  • Page 3 ULOS-CIR Series Occupant Sensors Sensors 369656b 3 05.04.12 Wiring Note: Power pack may be required when interfaced to lighting control system; see below. Single Sensor to System 2 or More Sensors to System Lighting Lighting control control system system To additional...
  • Page 4 ULOS-CIR Series Occupant Sensors Sensors 369656b 4 05.04.12 Wiring: Stand-Alone Control 1 to 3 Sensors with Power Pack 120 / 277 / 347 V 60 Hz; 230 V 50 / 60 Hz Neutral Black White Red (+20 - 24 V )
  • Page 5: Installation

    ULOS-CIR Series Occupant Sensors Sensors 369656b 5 05.04.12 Installation Sensor Placement • The occupant sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets, shelves, indirect hanging fixtures, etc. • Do not place sensor within 6 ft (1.8 m) of air vents, air handlers, windows, fans, etc., as this may cause false triggering.
  • Page 6 ULOS-CIR Series Occupant Sensors Sensors 369656b 6 05.04.12 Installation Mounting Mounting to Non-Standard Ceiling or Fixture Normal Mounting Mount twist-lock cover plate using mounting Twist and lock threaded mounting post onto cover screws, nuts, and washers (included). Drill/punch plate. Drill through ceiling tile with assembly, using cutter end of the threaded mounting post.
  • Page 7: Sensor Adjustments

    ULOS-CIR Series Occupant Sensors Sensors 369656b 7 05.04.12 Sensor Adjustments Override Settings Off (Default) Automatic (Normal) Manual on/off (Override) Auto/Manual Auto Threshold Adjustment High Sensitivity (Low turn-on threshold) Threshold Lights indicate motion Disable LED Indicator LED Motion Indicator Reset Learned Settings...