Download Print this page
olympia electronics GR-2100 Quick Start Quide

olympia electronics GR-2100 Quick Start Quide

Self testing maintained emergency luminary with wireless communication

Advertisement

Quick Links

SELF TESTING MAINTAINED EMERGENCY LUMINARY WITH WIRELESS COMMUNICATION
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Cd)
Tx/Rx frequency range
Tx power
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMY DURATION
ILLUMINATION SOURCE
ILLUMINATION (230V AC / emergency)
VEWING DISTANCE
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
Each luminaire must be permanently connected
to mains power supply. In normal operation the
illumination LEDs are lit as well as the green
indicating charge LEDs when the battery is
charging. In case of a mains power supply
failure, the luminaire
mode and will light automatically. When the
mains power supply is restored the device turns
to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
Battery Charging
The battery charging procedure is controlled by
the processor, thus maintaining its best possible
preservation, as it extends its duration.
Battery Cut-off
The luminaire enters this mode when the mains
power supply fails and battery has lost all its
energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Page 1 from 5
GR-2100/ST/M/WL
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2,
ΕΝ 61000-3-3, ETSI EN 303 446-1 v1.1.0, ETSI EN 300 220-2 v3.1.1
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
enters in emergency
(for LED MODULE Specs. see page 2)
220-240V AC/50-60Hz
3.3W / 3.6VA
3.6V/600mAh
868 - 870MHz
11dBm
Battery and charge Fault indication LEDs, TEST button
16 h
1.5 h
12 White LEDs
100lm / 100lm
22m
IP30
5 to 40 C
up to 95%
ABS/PC,PC
292 x 111 x 54 mm
476gr.
3 years (1 year for the battery)
Manual Operational Test
This test can be done by pressing the test
button. The light source and the emergency
circuit of the device are monitored for 3 sec. The
manual test can be conducted only if the mains
power supply and the battery are connected.
During this test period all indication LEDs are
OFF.
Automatic Operational Test
This test includes all the operations of the
manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected.
Automatic Autonomy Test
The Automatic Autonomy Test measures the
device's back up operation and emergency
duration. This test is conducted automatically
every 6 months. In order to be performed, the
mains power supply and the battery should be
connected and fully charged. If the battery is not
fully charged, the test is postponed until the
battery is completely charged. If during this test,
the autonomy is less than nominal, the battery
fault led turns on continuously and the battery
must be replaced.
GR-2110/ST/M/WL
3.6V/1.5Ah
24 h
3 h
o
557gr.
923211010_09_001

Advertisement

loading

Summary of Contents for olympia electronics GR-2100

  • Page 1 TYPICAL WEIGHT 3 years (1 year for the battery) GUARANTEE Thank you for your trust in our products Olympia Electronics - European manufacturer GENERAL Manual Operational Test These luminaires are used indoors (ta 40 C) This test can be done by pressing the test where emergency light is needed.
  • Page 2 4. Follow the step 6 of the installation procedure 3. In case of inactive use for a period greater and power the device. LED MODULE CHARACTERISTICS GR-2100/ST/M/WL GR-2110/ST/M/WL Olympia Electronics S.A Manufacturer Model Number 3105165 Voltage Range 8.7-10.8VDC Nominal Power...
  • Page 3 Button functionality: Wireless Communication indications (interior) The on-board button has the two following functions: 1. Short press (<2"): a status message will The top LED (LD3-green) indicates the be sent to the Gateway device of the network connection status. This LED may blink according to the wireless network.
  • Page 4: Installation Instructions

    INSTALLATION INSTRUCTIONS Figure 2 Figure 1 External switch Controled operation of the illumination source Battery’s connector Link Permanent Figure 3 operation of the illumination source Figure 4 1. To instal the device you have to dismantle carefully the device with a flat screwdriver as shown on figure 1.
  • Page 5: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-2100 stGr-2100 mGr-2100 wlGr-2110Gr-2110 stGr-2110 m ... Show all