Installation, Operation and Maintenance Manual
14.
Test the unit functions before turning the Mini-dap4 or dap4 controller on by performing the following
procedure.
a. Temporarily disconnect the J1 connector off the dap4 control module, turn the unit power ON.
b. Use the switches on the Manual Override Switch Board to turn on one function at a time (fan, cool, heat,
humidifier) to make sure they run properly.
15.
After the manual override testing, turn the power OFF and reconnect the J1 connector back to the dap4 or
Mini-dap4 control module.
16.
Turn the unit power back ON and wait for about 30 seconds for the dap4 or Mini-dap4 to go through its
self-test. During this time, the backlit display will light without text. After the self-test, the dap4 will display
text. Press and hold the ESC key for 5 seconds to start the unit.
17.
If field adjustments to the settings have been made, these must be reloaded after the new controller is in
place and operational. Refer to dap4 or Mini-dap4 User Manual for programming details.
18.
Check all sensors and options are operating correctly.
8 Low Ambient Receiver Package
NOTICE. The pressure relief valve line must be vented to the atmosphere per
latest of ASHRAE Standard 15 and or any local Building, Fire, or Mechanical
Codes.
NOTICE. As a minimum, the installer should wear thermal protective gloves and
face-shield/goggles when working with refrigerant. Application of excessive
heat to any component will cause extreme pressure and may result in a rupture.
Exposure of refrigerant to an open flame or a very hot surface will cause a
chemical reaction that will form a highly poisonous and corrosive gas commonly
referred to as PHOSGENE. In its natural state, refrigerant is a colorless, odorless
vapor. It is heavier than air and will disperse rapidly in a well-ventilated area. In
an unventilated area, it presents a danger.
NOTICE. Before carrying out the pressure test, precautions shall be taken to
evacuate all personnel from the area of risk and post notices advising that the
system or equipment is under pressure.
Page 75 of 100
Need help?
Do you have a question about the gPod and is the answer not in the manual?