Do you have a question about the Hydrawise HCC-800-PL and is the answer not in the manual?
Questions and answers
ivan kozina
March 12, 2025
I need help. When, for example, line 1 is activated, the valve opens, but the pump does not start. By measuring the voltage, we determined that there is no 24V at the P/MW output. Is it necessary to adjust the program and add the pump start-up?
1 comments:
Mr. Anderson
March 12, 2025
Yes, the Hunter Hydrawise HCC-800-PL requires program adjustments to enable pump start-up. You need to configure the pump start relay (PSR) setting in the software. This can be done by editing the zone settings in the ZONES AND SCHEDULES section under ADVANCED SETTINGS. If using an HC Hydrawise controller, any of the available zones can be set to act as the pump start relay, typically assigned to the last unused zone.
Need help?
Do you have a question about the Hydrawise HCC-800-PL and is the answer not in the manual?
Questions and answers
I need help. When, for example, line 1 is activated, the valve opens, but the pump does not start. By measuring the voltage, we determined that there is no 24V at the P/MW output. Is it necessary to adjust the program and add the pump start-up?
Yes, the Hunter Hydrawise HCC-800-PL requires program adjustments to enable pump start-up. You need to configure the pump start relay (PSR) setting in the software. This can be done by editing the zone settings in the ZONES AND SCHEDULES section under ADVANCED SETTINGS. If using an HC Hydrawise controller, any of the available zones can be set to act as the pump start relay, typically assigned to the last unused zone.
This answer is automatically generated