Download Print this page

Siemens RDF301 Quick Start Manual page 10

Semi flush-mount room thermostats with knx communications
Hide thumbs Also See for RDF301:

Advertisement

Operational data
Environmental conditions
Standards and directives
10 / 14
Siemens
Building Technologies
Switching differential, adjustable
Heating mode
Cooling mode
Setpoint setting and range
Comfort
Economy
Protection
Multifunctional input X1/X2
Input X1 default value
Input X2 default value
Built-in room temperature sensor
Measuring range
Accuracy at 25 °C
Temperature calibration range
Settings and display resolution
Setpoints
Current temperature value displayed
Operation
Climatic conditions
Temperature
Humidity
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Storage
Climatic conditions
Temperature
Humidity
conformity
EMC directive
Low-voltage directive
C-tick conformity to EMC emission standard
Reduction of hazardous substances
Product standards
Automatic electrical controls for household and
similar use
Special requirements for temperature-dependent
controls
Electronic control type
Home and Building Electronic Systems
Electromagnetic compatibility
Emissions (residential)
Immunity (industrial and residential)
Safety class
Pollution class
Degree of protection of housing
RDF301. / RDF301.50 / RDF600KN
Semi flush-mount room thermostats with KNX communications
(P30)
2 K (0.5...6K)
(P31)
1 K (0.5...6K)
(P08)
21°C
(P11-P12)
15°C/30°C (OFF, 5...40 °C)
(P65-P66)
8°C/OFF
Selectable 0...8
(P38)
3 (Operating mode
switchover)
(P40)
1 (External temperature
sensor)
0...49 °C
< ± 0.5 K
± 3.0 K
0.5 °C
0.5 °C
As per IEC 721-3-3
Class 3K5
0...50 °C
<95 % r.h.
As per IEC 721-3-2
Class 2K3
25...60 °C
<95 % r.h.
Class 2M2
As per IEC 721-3-1
Class 1K3
25...60 °C
<95 % r.h.
2004/108/EC
2006/95/EC
AS/NZS 61000.6.3: 2007
2002/95/EC
EN 60730–1
EN 60730–2-9
2.B (micro-disconnection on
operation)
EN 50090-2-2
IEC/EN 61000-6-3
IEC/EN 61000-6-2
II as per EN 60730
Normal
IP 30 as per EN 60529
(5...40 °C)
(OFF, 5...40 °C)
CE1N3171en
2012.10-04

Advertisement

loading

This manual is also suitable for:

Rdf301.50Rdf600kn