WARNINGS
• TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE
AND TEST THAT POWER IS OFF BEFORE WIRING!
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
• To avoid electrical overload, total connected lamp load shall not exceed output rating.
• This equipment permits more than one power supply output source.
• Do not mount near gas or electric heaters.
Product Description
The GreenMAX™ DRC Phase Cut Dimmer provides dimming of phase control loads,
either forward or reverse phase, LumaCAN network connectivity, and full integration
into Leviton's GreenMAX DRC system.
Before Installation
• Dimmer modules should be installed in a suitable DIN rail enclosure.
• All mains wiring should be done in accordance with local authority wiring regulations.
• Appropriate isolation shall be maintained between Line and Low Voltage cabling.
• For more information on network wiring, see the Leviton GreenMAX DRC Installation Guide
and training videos at www.Leviton.com.
• Confirm load type and amount is within product capabilities as not all load types are supported.
• Confirm Channel/Load requirements to plan for installation, when multiple channels are to be combined
for additional current capacity, refer to AMPlify feature for details.
Load 1
10A MAX
Neutral
Line In
Channel Jumper
Wiring Diagrams
EARTH
LOAD OUT 1
NEUTRAL
LOAD OUT 2
NEUTRAL
GND
STATUS
TEMP
NET
MODE
1
2
3
TEST
AUX. IN
A
B
2 Channel (1x2.5A,1x7.5A)
Load 1
2.5A MAX
NEUTRAL
LOAD OUT 1
NEUTRAL
LOAD OUT 2
3 Channel (2x2.5A, 1x5A)
Load 2
2.5A MAX
Load 1
2.5A MAX
NEUTRAL
LOAD OUT 1
NEUTRAL
LOAD OUT 2
Installation
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER at circuit breaker or fuse and test that power is off before wiring!
1.
Mount dimmer on DIN rail.
a. Line top of module against the back of the cabinet and
slide the module down onto rail.
b. Push module towards the rail.
c. Push up on mounting clip to lock module in place.
2.
Remove/add channel jumpers depending on configuration.
3.
Wire "feeder" input to Line Input Terminal.
4.
Connect Loads to Load Output Terminals.
5.
Connect Network Wiring.
6.
Power-up dimmer and confirm load operation using dimmer test
switches. Your Dimmer is now ready for network configuration.
Note: Ensure last node on network is terminated.
© 2018 Leviton Mfg. Co., Inc.
LumaCan™ Phase Cut Dimmer
Channel Jumper
Channel Jumper
LINE IN
NEUTRAL
LOAD OUT 3
LOAD OUT 4
NEUTRAL
4
Bus network cable
(CAT 6A or better)
Load 2
7.5A MAX
Neutral
Line In
Channel Jumper
Channel Jumper
EARTH
NEUTRAL
LINE IN
NEUTRAL
LOAD OUT 3
GND
STATUS
TEMP
NET
MODE
1
2
3
4
TEST
Load 3
5.0A MAX
AUX. IN
A
B
Neutral
Line In
Bus network cable
Channel Jumper
(CAT 6A or better)
EARTH
NEUTRAL
LINE IN
NEUTRAL
LOAD OUT 3
NEUTRAL
GND
STATUS
TEMP
NET
MODE
1
2
3
4
TEST
AUX. IN
A
B
Bus network cable
(CAT 6A or better)
Cat. No. DRDDP
INSTALLATION INSTRUCTIONS
CAUTIONS
• Use this device with copper or copper clad wire only.
• For indoor applications only.
• Test all network cables for proper pin-out configuration prior to interconnecting devices and systems.
• If you are unsure about any part of these instructions, consult an electrician.
• Save these instructions.
Catalog No.
Input Voltage/Frequency
Max Input Current
Load Ratings
LED,CFL, Electronic Ballast,
Incandescent, Tungsten @ 120V
LED,CFL, Electronic Ballast,
Incandescent, Tungsten @ 277V
IP Rating / Enclosure
Pollution Degree
UL Disconnection Type
UL Voltage Category
Terminal Torque Rating,
Line & Low Voltage
Network Connections
Network Topology
Operating Temperature
(In DIN rail cabinet)
Storage Temperature
Certifications
1 Channel (10A)
NEUTRAL
2 Channel (5A)
NEUTRAL
LOAD OUT 4
NEUTRAL
4 Channel (2.5A)
LOAD OUT 4
NEUTRAL
a.
b.
DIN rail
c.
SPECIFICATIONS
DRDDP-A40 (4 Channel)
120-277VAC, 50/60Hz
10A
2.5A (300W)/Channel
(See channel ganging chart for additional details)
2.5A (693W)/Channel
(See channel ganging chart for additional details)
IP20
2
Type 1Y Action, Electronic Disconnection, Non-Airgap
6,000V
0.37in-lbs (0.5Nm)
(2) RJ-45, CAT6A or better for connection to LumaCAN
network. Termination provided via local termination plug.
• Daisy Chain, 1600' Max between repeaters.
• Home-Run topology and network length up to 10,000'
can be achieved when using LumaCAN network repeaters
(Leviton # NPRPT)
• Maximum 110 nodes between repeaters
Maximum 250 nodes on a LumaCAN network
0-60
o
C (32-140
-40-70
C
o
FCC Part 15 Class A
Load 1
10A MAX
Neutral
Channel Jumper
EARTH
LOAD OUT 1
NEUTRAL
LOAD OUT 2
NEUTRAL
GND
STATUS
TEMP
NET
MODE
1
2
TEST
Load 1
Neutral
5.0A MAX
AUX. IN
A
B
Channel Jumper
EARTH
LOAD OUT 1
NEUTRAL
LOAD OUT 2
NEUTRAL
GND
STATUS
TEMP
NET
MODE
1
2
TEST
Load 2
2.5A MAX
AUX. IN
Neutral
A
B
Load 1
2.5A MAX
EARTH
LOAD OUT 1
NEUTRAL
LOAD OUT 2
NEUTRAL
GND
STATUS
TEMP
NET
MODE
1
2
TEST
AUX. IN
A
B
DI-002-DRDDP-00A-X3
ENGLISH
DRDDP-A20 (2 Channel)
120-277VAC, 50/60Hz
5A
o
F)
Line In
Channel Jumper
Channel Jumper
LINE IN
NEUTRAL
LOAD OUT 3
NEUTRAL
LOAD OUT 4
3
4
Load 2
Line In
5.0A MAX
Channel Jumper
Bus network cable
(CAT 6A or better)
LINE IN
NEUTRAL
LOAD OUT 3
LOAD OUT 4
NEUTRAL
3
4
Load 4
2.5A MAX
Line In
Load 3
2.5A MAX
Bus network cable
(CAT 6A or better)
LINE IN
NEUTRAL
LOAD OUT 3
NEUTRAL
LOAD OUT 4
3
4
Bus network cable
(CAT 6A or better)
To remove
from DIN rail
DI-002-DRDDP-00A-X3