Address Setup; Check At Main Power-On - Toshiba MMY-MAP1404 Series Quick Reference

Super modular multi system
Table of Contents

Advertisement

Address Setup

Check at Main Power-on

After turning on the main power of the indoor units and outdoor unit in the refrigerant line to conduct a test
operation, check the following items in each outdoor and indoor unit.
(After turning on the main power, be sure to check in order: indoor unit → outdoor unit.)
<Check on the outdoor unit>
(1) Check that all the rotary switches, SW01, SW02, and SW03, on the interface PC board of the header unit are
set to "1."
(2) If another check code is displayed on the 7-segment display [B], remove the cause of the problem referring to
Section, "TROUBLESHOOTING".
(3) Check that "L08" is displayed on the 7-segment display
Indoor address not set up)
(If the address setup operation has already been completed during servicing, etc., the above check code is not
displayed, and only "U1" is displayed on the 7-segment display [A].)
Interface PC board
<Check on the indoor unit>
(1) Display check on the remote controller (in the case of a wired remote controller)
Check that a frame, as shown in the following figure at left, is displayed on the LC display section of the remote
controller.
Good
TEMP.
FILTER
RESET
TEST
Normal status
(Power suppl ied and operation stopped)
If no frame is displayed, as shown in the above figure at right, the remote controller does not have a normal
supply of power; check the following items.
• Check the power supply of the indoor unit.
• Check the wiring between the indoor unit and the remote controller.
• Check whether there is a cutoff of wire around the indoor control PC board or not, and check for connection
failures of the connectors.
• Check for failure of the transformer for the indoor electrical control box.
• Check for failure of the indoor control PC board
Push switches
7-segment display
[A]
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
SET
CL
SWING/FIX
UNIT LOUVER
[B]
on the interface PC board of the header unit. (L08:
SW04
SW05
SW15
D600 D601 D602 D603 D604
SW01 SW02 SW03
Rotary switches
No good
TEMP.
FILTER
RESET
TEST
When power is not supplied normally
7-segment display
[B]
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
SET
CL
SWING/FIX
UNIT LOUVER
08

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents