Wiring Diagram - Panasonic FY-E15PM1 Operation Instruction Manual

Energy recovery ventilator
Table of Contents

Advertisement

WIRING DIAGRAM

Wiring diagram
Supplied
Power
for Air
Conditioner
220V ~
50Hz
controller for
air conditioner
(Customer Provide)
Air Conditioner
Power
220V ~
50Hz
Double Pole Switch
(Customer Provide)
(Contact Point Separate
Distance Over 3mm)
Precaution during the wire connection:
The dashed line shown in wiring diagram must be conducted by authorized person.
Please use the switch with contact point separation distance above 3mm.
Please use the switch with rate current above 10A.
It's recommended to use the wire (soft wire) with rate voltage 300V/500V to link power supply cord with switch as
stipulated in 60227IEC 53.
Power supply cord should be 3 core wires containing green/yellow wire, besides, please use the 2 core wire to
link the terminal SW1, SW2 with switch, each core wire should have cross section area 2.5mm
air conditioner is applied, please use the 2 core wire. (if not using this function,please omit the connection.)
Main Unit
Air Conditioner
Contact point a
without voltage
Damper
Switch
Second Main Unit
Orange
Brown
Black
Black
Black
A2
Brown
A1
Blue
Red
Black
Blue
HI
Gray
White
LO
Black
Black
Black
COM
Orange
White
SW2
Black
Black
Gray
SW1
Red
White
N
Black
L
Terminal Block
Terminal Block
L
N
SW1 SW2 COM LO
Third Main Unit
Wirig diagrams of left type and right type are symmetrical.
7
4
8
6
Black
2
3
5
1
Relay 3
Black
4
Black
Black
3
7
4
8
Yellow
Yellow
2
6
2
3
White
White
1
5
1
Relay 2
Connector
Connector
Capacitor
Orange
Red
7
4
8
Yellow
(
Yellow
LO
6
2
3
(
)
Red
Blue
HI
5
1
White
(
SHI
Relay 1
Connector
Connector
Damper
HI
Damper
Motor
Blue
4
Black
3
Yellow
2
White
1
Limit Switch
Black
6
Orange
5
Red
4
Motor
)
Yellow
3
Blue
2
)
White
1
A1 A2
, if interlock with
2