Table 6 Rating Of Contactors And Fuses - Mitsubishi Electric 1100B Series Owner Technical Manual

Table of Contents

Advertisement

Table 6 Rating of Contactors and Fuses▲

Component
Description
UPS Rating (kVA)
Static Bypass Input
CB3
Contactor
Static Bypass
52S
Contactor
F6,F7,F8
AC Input Fuse
F4,F5
Battery Input Fuse
F9,F10,F11
AC Output Fuse
F2,F3
Control Power
F1
Control Power
▲ For other stored energy systems, refer to the supplement.
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
Component Rating @ 208V, 3-phase, 60 Hz
10
20
135A
135A
285A
285A
MITSUBISHI ELECTRIC 1100B SERIES UPS
30
40
50
135A
135A
135A
285A
285A
285A
660V / 60A
660V / 60A
660V / 60A
250V / 2A
500V / 5A
Page Number:
1-19
60
70
80
135A
135A
135A
285A
285A
285A

Advertisement

Table of Contents
loading

Table of Contents