Figure 3 Single Line Diagram - Emergency Operation - Mitsubishi Electric 1100B Series Owner Technical Manual

Table of Contents

Advertisement

C) Emergency Operation: Load power supplied by UPS battery.
CB
Bypass
input
User
supplied
MCCB
CB
AC
input
User
supplied
MCCB
Referring to Figure 3: In the event of an AC input source failure or interruption, the UPS
converter will de-energize and the UPS battery will immediately discharge and supply DC
power to the inverter to maintain continuous AC power to the load. This operation will continue
until:
a) The battery capacity expires and the inverter turns off, or
b) The input power is restored after which the converter will simultaneously power the inverter
and critical load and recharge the batteries.
A fully charged battery will provide power for the specified time at the rated load, or longer, at a
reduced load.
When power is restored after a low battery shutdown, the UPS converter automatically restarts
operation, the charger recharges the batteries and the Inverter is automatically restarted without
operator intervention. The load is automatically assumed by the inverter without operator
intervention.
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL

Figure 3 Single Line Diagram - Emergency Operation

UPS Module
CONVERTER /
CHARGER
52RC
72B
BATTERY
MITSUBISHI ELECTRIC 1100B SERIES UPS
52S
CB 3
Static Transfer
Switch
INVERTER
52 C
Power Flow
Not in Use
External Battery
Page Number:
1-13
Output