Table 5 Detail Of Specifications - Mitsubishi Electric 1100B Series Owner Technical Manual

Table of Contents

Advertisement

Table 5 Detail of Specifications▲

Type
Rated Output kVA
Rated Output kW
Configuration
Voltage
Frequency
Reflected Current THD
Configuration
Voltage
Frequency
Configuration
Voltage
Voltage Stability
Frequency
Frequency Stability
Power Factor
Power Factor range
Voltage THD
Transient Response
Transient Recovery
Voltage Unbalance
Voltage Phase Angle
Displacement
Inverter Overload
System Overload
Crest Factor
Capabilities
Cooling
Operating Temperature
Relative Humidity
Altitude
Location
Paint Color
▲ For other stored energy systems, refer to the supplement.
1100B SERIES UPS
OWNERS / TECHNICAL MANUAL
UP1133B-
UP1133B-
UP1133B-
A103SU-2
A203SU-2
A303SU-2
10
20
30
9
18
27
AC INPUT CHARACTERISTICS
3-phase, 3-wire, plus ground
120/208 V
+15% ~ -30%
60 Hz +/- 10%
4% typical at 100% load; 7% typical at 50% load
BYPASS INPUT
3-phase, 4-wire, plus ground
120/208 V
+10%
60 Hz +/- 10%
AC OUTPUT
3-phase, 4-wire
120/208 V
+/-1%
60 Hz
+/-0.01% in free running mode
0.9 nominal
0.9 ~ 1.0 lagging (within output kW rating)
2% typical THD at 100% linear load
5% typical THD at 100% non-linear load
+/-3% typical at 100% load step
+/-1% typical at loss/return of AC power
+/-5% typical at load transfer to/from static bypass
16.7 ms
+/-2% typical at 100% unbalanced load
+/-1deg. typical at 100% load
105% to 125% for 60 seconds; 126% to 150% for 30 seconds
1000% for 1 cycle (with bypass available)
2.5 : 1
ENVIRONMENTAL
Forced Air
41 deg F ~ 95 deg F (5 deg C ~ 35 deg C).
Recommended 68 deg F ~ 77 deg F (20 deg C ~ 25 deg C)
5% ~ 95% Non-Condensing
Will vary with model
Temperature-controlled, indoor area free of conductive contaminants
Munsell N1.5 (Black)
MITSUBISHI ELECTRIC 1100B SERIES UPS
UP1133B-
UP1133B-
UP1133B-
A403SU-2
A503SU-2
A603SU-2
40
50
60
36
45
54
Page Number:
1-18
UP1133B-
UP1133B-
A703SU-2
A803SU-2
70
80
63
72