Table 1.5 Rating Of Circuit Breakers (Mccb) - Mitsubishi Electric 9700 Series Owner Technical Manual

Uninterruptible power supply system
Hide thumbs Also See for 9700 Series:
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC
TABLE 1.5 Rating of Circuit Breakers (MCCB) and Fuses
NUMBER
M
CB1
AC input circuit breaker
C
52RC
Battery disconnect circuit
C
CB2
B
CB101
FCU, FCV, FCW,
F
FCX, FCY, FCZ
Converter main circuit fuse
FIU, FIV, FIW,
U
FIX, FIY, FIZ
Inverter main circuit fuse
(OPTION)
FSU, FSV, FSW
Bypass main circuit fuse
S
FUD1, 2
E
FUS1, 2, 3
Bypass input ZNR fuse
S
FZS1, 2, 3
Bypass input ZNR fuse
FBS1, 2
CB3 control circuit fuse
FZC1, 2, 3
Get user manuals:
See SafeManuals.com
OWNERS / TECHNICAL MANUAL
APPLICATION
100kVA
208V
480V
-
AC input contactor
350A
breaker
400A
Control circuit breaker
450A
450A
450A
Control power fuse
DC500V 3A
AC600V 10A
AC600V 30A
AC600V 5A
AC input ZNR fuse
AC600V 30A
9700 SERIES UPS
OUTPUT CAPACITY OF EQUIPMENT
150kVA
600V
208V
480V
600V
-
-
-
-
-
420A
600A
15A
630A
630A
-
630A
-
DC500V 3A
AC600V 10A
AC600V 30A
AC600V 5A
AC600V 30A
MITSUBISHI ELECTRIC 9700 SERIES UPS
Page Number:
225kVA
300kVA
208V
480V
600V
480V
600V
-
-
-
600A
400A
660A
-
800A
1200A
900A
900A
900A
900A
900A
-
-
DC500V 3A
DC500V 3A
AC600V 10A
AC600V 10A
AC600V 30A
AC600V 30A
AC600V 5A
AC600V 5A
AC600V 30A
AC600V 30A
1-11
375kVA
480V
600V
800A
600A
-
1600A
30A
800A
800A
-
DC500V 3A
AC600V 10A
AC600V 30A
AC600V 5A
AC600V 30A

Advertisement

Table of Contents
loading

Table of Contents