Table 1.5 Detail Of Specifications - Mitsubishi Electric 9900B Series Owner Technical Manual

Uninterruptible power supply system
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC

Table 1.5 Detail of Specifications▲

Rated Output kVA
Rated Output kW
Configuration
Voltage
Frequency
Reflected Current THD
Configuration
Voltage
Frequency
Type
Ride Through
Nominal Voltage
Minimum Voltage
Number of Cells
Configuration
Voltage
Voltage Stability
Frequency
Frequency Stability
Power Factor
Power Factor Range
Voltage THD
Transient Response
Transient Recovery
Voltage Unbalance
Voltage Phase Angle
Displacement
Inverter Overload*
System Overload
(with bypass available)
Cooling
Operating Temperature
Relative Humidity
Altitude
Location
Paint Color
*Voltage regulation maintained
▲ For other stored energy systems, refer to the attached supplement.
9900B SERIES UPS
OWNERS / TECHNICAL MANUAL
300
300
AC INPUT
3 phase, 3 wire
480 V
+15% to -20%
60 Hz +/-10%
3% max. at 100% load
5% max. at 50% load
STATIC BYPASS INPUT
3 phase, 3 wire
480 V
+/-10%
60 Hz +/-5%
BATTERY
Lead Acid
Application Specific
480 Vdc
400 Vdc
240
AC OUTPUT
3 phase, 3 wire
480 V
+/-1%
60 Hz
+/-0.01% in free running mode
Unity (nominal)
0.7 lagging to 0.8 leading
2% maximum THD at 100% linear load
5% maximum THD at 100% non-linear load
+/-2% maximum at 100% load step
+/-1% maximum at loss/return of AC power
+/-5% maximum at load transfer to/from static bypass
Less than 20ms
2% maximum at 100% unbalanced load
+/-1deg. maximum at 100% load
105% to 109% for 1-hour duration
110% to 124% for 10-minute duration
125% to 149% for 1-minute duration
1000% for 1 cycle
ENVIRONMENTAL
Forced Air
41゚F to 95゚F ( 5゚C to 35゚C).
Recommended : 68゚F to 77゚F ( 20゚C to 25゚C)
5% ~ 85% Non-Condensing
Operating altitude: Sea Level to 2250 meter (7400ft)
Indoor (free from corrosive gases and dust)
Munsell 5Y7/1 (Beige)
MITSUBISHI ELECTRIC 9900B SERIES UPS
Page Number:
500
500
500% for 1 cycle
1-21
750
750