Intermatic IOS-CMP-LV Installation And Configuration Instructions page 2

360 passive infrared low voltage occupancy sensor with light level feature

Advertisement

ADJUSTING DIP SWITCH SETTINGS
The occupancy sensor features 9 DIP switches. Each setting can be set to an up position or down position that
configures the DIP Switch setting to a specified requirement. Follow this procedure to adjust the DIP switch settings.
1. Adjust the sensitivity level DIP Switch (1). The Up position sets the sensitivity to 100%, while the down position
adjusts the sensitivity level to 50%.
2. Adjust the time delay DIP switches (2-4). Refer to the table for a list of the time delay options.
NOTE: After the sensor detects no motion in the coverage area, it will delay a user-configured amount of time before turning lights off. See the table before turning
lights off. See the table below to determine how to set the desired time delay for the sensor.
Time Delay
15 Sec/Autoset
30 Seconds
5 Minutes
10 Minutes
15 Minutes
20 Minutes
25 Minutes
30 Minutes
3. Adjust Dip switch settings 5 through 9. See table 2 below for a description of each setting.
NOTE: For DIP switch settings 5 through 9, the up position enables the setting, while the down position disables the setting.
DIP
SWITCH
NUMBER
5
Walk Through - Turns the lights off for three minutes after the area is initially occupied.
If no motion is detected.
6
Vacancy - Turn this DIP switch to ON if you have a momentary switch. This enables overrides.
7
Audible Alert - An alarm (sounds like a tick) that indicates that the time delay has expired.
8
Visible Alert - An alarm (load LED flashes once) to indicate the time delay has expired.
9
Hold ON - Set this to ON to override all sensor functions
4. Install the front on the sensor and secure with the screws.
TESTING THE OCCUPANCY SENSORS
1. Ensure the PIR Activity is enabled Red LED flashes, Hold ON mode is OFF (DIP 9 switch OFF) and PIR Sensitivity is set to MAX (DIP switch 1 ON).
2. Make sure DIP Switches 2, 3, and 4 are set to the down (disable) position so the Time Delay is set for TEST MODE with the 15 seconds/AUTOSET setting.
3. Ensure the Light Level is the default (maximum).
4. Do not move so the sensor doesn't detect the movement. The green LED and Load are ON and the lights should turn off after 15 seconds.
5. Move about the coverage area. The lights will illuminate.
6. When testing and adjustment is complete, reset DIP Switches and Light Level to the desired settings and replace the cover on the sensor.
NOTE: If you need to invoke the Test Mode and the DIP switches are already set for 15 seconds/Autoset, toggle DIP switch #3 ON the back to the OFF position. This
provides a 5-minute test period. During the test period, the Time Delay is only 15 seconds.
The PIR activity LED does not flash properly,
There is improper PIR activity, LED flashes
Lights do not turn on automatically
The sensor is activating without detecting movement
Warranty service is available by either (a) returning the product to the dealer from whom the unit was purchased or (b) completing a warranty claim online at www.intermatic.com. This warranty is made by: Intermatic
Incorporated, 1950 Innovation Way, Suite 300, Libertyville, IL 60048. For additional product or warranty information go to: http://www.Intermatic.com or call 815-675-7000.
DIP SWITCH 1 - SENSITIVITY LEVEL SETTINGS
50%
100%
TIME DELAY SETTINGS
2 Switch Setting
Down Position
Down Position
Down Position
Down Position
Up Position
Up Position
Up Position
Up Position
DESCRIPTION
TROUBLESHOOTING
The warm-up period has not been completed
Make sure the circuit breaker is on
Set the PIR sensitivity to Max/Autoset (DIP switch 1 ON)
Check all sensor and power pack connections
Check for 24V input to the sensor. If 24V is present, replace the sensor. If 24V is not present, check if the high
voltage is present to power pack. If it is, replace the power pack.
Make sure the light level adjustment is set properly by covering the PIR lens and PIR activity LED to verify if lights
turn on. If lights still turn on, adjust the light level.
Check all sensor and power pack wire connections.
While the sensor is activated, check for 24 V DC at the blue wire connection at the sensor. If there is no voltage,
replace the sensor. If voltage is present, replace the power pack.
Make sure the sensor is not experiencing activations from outside the controlled area
Check all sensor and power pack wire connections
Disconnect the blue wire. If lights do not turn off, replace power pack. If lights turn off, check the sensor.
Turn the sensitivity and time delay to minimum and allow the sensor to time out.
Set the DIP switch 1 to OFF
Relocate the sensor.
LIMITED WARRANTY
Up Position
Down Position
Settings Chart
Down position
Up Positions
3 Switch Setting
Down Position
Down Position
Up Position
Up Position
Down Position
Down Position
Up Position
Up Position
Enable the Setting. Set
DIP Switch To
Up Position
Up Position
Up Position
Up Position
Up Position
DIP SWITCH
ON
DIP Switch
1
2
3
4
5
6
7
8
9
Settings
2
3
4
5
6
7
8
9
1
4 Switch Setting
Down Position
Up Position
Down Position
Up Position
Down Position
Up Position
Down Position
Up Position
Disable the Setting. Set
DIP Switch To
Down Position
Down Position
Down Position
Down Position
Down Position
158--02108REF