Outdoor Unit Installation; Mounting The Outdoor Unit - Samsung AR Series Technical Data Book

Rac for europe nordic (inv, r32, 50hz, hp)
Hide thumbs Also See for AR Series:
Table of Contents

Advertisement

11. Installation

Outdoor Unit Installation

Mounting the outdoor unit

To promote proper condensate draining, the
recommended installation of the outdoor unit is
elevated above the ground on a mounting bracket
attached to a concrete pad.
In areas where snowfall occurs, the unit must be
mounted above the snow line to allow for proper
heating. Snow cannot be allowed to collect on top of the
unit. For promoting natural drainage in a heavy snow
fall area:
• Make space more 80 mm between the bottom of the
outdoor unit and the ground for installation. (Ensure
that the drained water runs off correctly and safely.)
• Allow enough separation distance between the
product and the ground.
80 mm
※ In case you want more information about the controllers and accessories, please refer to the Controller and
Accessory TDB on pvi.Samsung.com site or Global Partner Portal site.
Snow-proof
hood
Estimated
snow fall
Ground
On the ground
1 Place the outdoor unit in the selected installation
location (Step 1.1 on page 93), ensuring proper
clearances and with the arrow on top of the unit
pointing away from the wall.
2 Clip the rubber feet to the tabs to minimize sound
and vibration to the structure.
Model
**09*******
**12*******
3 Level the unit, then use anchor bolts to secure it at
the four mounting points.
4 For installations in locations that require seismic or
hurricane tie downs, comply with local codes.
5 If the selected location is exposed to strong winds,
install a protective fence around the unit so that the
fan can operate correctly.
X
Rubber leg
(Unit: mm)
X
Y
602
310

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents