REMOVE SERVICE PANEL
(1/4 TURN FASTENERS)
Interlock
These units have an interlock circuit incorporated into the control circuit, brought
out to two terminals. These terminals are shorted out for factory testing.
On site the shorting loop is to be removed and two wires taken to a pair of
volt free contacts in the water pump starter/contactor/relay or flow switch so
that the heat pump cannot operate unless the water pump is operating. (See
figures 5 & 6).
SD331851 ISSUE 28
LOCATION OF ELECTRICAL SUPPLY CONNECTIONS
IN CALOREX HEAT PUMP AW3034/7034
MAKE MAINS IN EARTH
CONNECTION HERE
MAINS SUPPLY IN
Fig. 4B
MAINS TERMINAL BLOCK
AND EARTHING POINT
(ALSO EXTERNAL INTERLOCK)
2 3 4 5 6 7 8
9 1011
POOL PUMP
INTERLOCK
SMART
OR
CLOCK
N
FLOW SWITCH
L1
SOFT
SOFT
L2
L3
EARTH
STUD
13