Mitsubishi Electric City Multi PUMY-P250YBM Installation Manual page 14

Hide thumbs Also See for City Multi PUMY-P250YBM:
Table of Contents

Advertisement

4. Installing the refrigerant piping
4.1.3-4 Selecting pipe size (Fig. 4-7)
System pipe size
A
A
E
C
B
b
c
a
E
E
E
en
Branch box pipe size
(1) Valve size of branch box for outdoor unit
For liquid
For gas
(2) Valve size of branch box for indoor unit
Liquid pipe
A UNIT
Gas pipe
Liquid pipe
B UNIT
Gas pipe
Liquid pipe
C UNIT
Gas pipe
Liquid pipe
D UNIT
Gas pipe
Liquid pipe
E UNIT
Gas pipe
* 3-branch type : only A, B, C unit
Branch box
Port A
Port B
Port C
Port D
Port E
13
A Outdoor unit
B First joint
C Branch header
D Branch box
E City Multi Indoor unit
F M series Indoor unit
C
D
D
d
e
f
g
h
i
E
E
F
F
F
F
Fig. 4-7
ø9.52 mm
ø15.88 mm
ø6.35 mm
ø9.52 mm
ø6.35 mm
ø9.52 mm
ø6.35 mm
ø9.52 mm
ø6.35 mm
ø9.52 mm
ø6.35 mm
ø12.7 mm
A
Model
Liquid pipe
P250
ø9.52*
P300
ø12.7
B, C, D, E
Total down-stream capacity
of indoor units
– 16.0 kW
16.1 kW – 22.4 kW
22.5 kW – 36.4 kW
36.5 kW –
j
* ø12.7 when connecting the indoor unit for PEFY-P200 or P250.
a, b, c – j
Indoor unit series
F
City Multi
M series
2-branch joint
4-branch header
8-branch header
Different-diameter joint (optional parts) (Fig. 4-4, 4-5)
Connected pipes diameter
Model name
MAC-A454JP
MAC-A455JP
MAC-A456JP
PAC-493PI
PAC-SG76RJ-E
PAC-SG75RJ-E
PAC-SG71RJ-E
PAC-SG77RJ-E
*1 When connecting to MSDD-50AR-E or a branch box, flare the pipes on-site.
Use the nuts that are included with the 2-branch pipe and branch box.
*2 Brazing
2 branch pipe (Joint) : Optional parts (According to the connection method,
you can choose the favorite one.)
Model name
MSDD-50AR-E
MSDD-50BR-E
Gas pipe
ø22.2
ø25.4
Model
Liquid pipe
P250
ø9.52*
P300
ø12.7
P250
ø9.52*
P300
ø12.7
P250
ø9.52*
P300
ø12.7
P300
ø12.7
Model number
A Liquid pipe
10 – 50
ø6.35
63 – 140
ø9.52
200
ø9.52
250
ø9.52
15 – 42
ø6.35
50
ø6.35
CMY-Y62-G-E
CMY-Y64-G-E
CMY-Y68-G-E
Diameter A
mm
mm
ø9.52
→ ø12.7
ø9.52
ø12.7
→ ø9.52
ø12.7
ø12.7
→ ø15.88
ø12.7
ø6.35
→ ø9.52
ø6.35
ø9.52
→ ø15.88
ø9.52
ø15.88
→ ø19.05
ø15.88
ø15.88 *1 → ø22.2 *2
ø15.88 *1
ø15.88 *1 → ø25.4 *2
ø15.88 *1
Connection method
flare
brazing
Gas pipe
ø15.88
ø19.05
ø22.2
ø25.4
B Gas pipe
ø12.7
ø15.88
ø19.05
ø22.2
ø9.52
ø12.7
Diameter B
mm
ø12.7
ø9.52
ø15.88
ø9.52
ø15.88
ø19.05
ø22.2 *2
ø25.4 *2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

City multi pumy-p300ybm

Table of Contents