• Do not vent R410A into the atmosphere.
Confirmation of parts attached
In addition to this manual, the following part is supplied with the outdoor unit.
It is used for grounding the S terminal of transmission terminal block TB7.
For details refer to "6. Electrical work".

1. Safety precautions

► Before installing the unit, make sure you read all the "Safety precau-
tions".
► Please report to or take consent by the supply authority before con-
nection to the system.
► Equipment complying with IEC/EN 61000-3-12
► It is designed for use in the residential, commercial and light-indus-
trial environment.
en
► PUMY-P250YBM, PUMY-P300YBM
"This equipment complies with IEC 61000-3-12 provided that the
short-circuit power S
is greater than or equal to S
sc
interface point between the user's supply and the public system. It is
the responsibility of the installer or user of the equipment to ensure,
by consulation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a short-circuit
power S
greater than or equal to S
sc
S
(*1)
sc
Model
PUMY-P250YBM
PUMY-P300YBM
Warning:
• T he unit must not be installed by the user. Ask a dealer or an authorized
technician to install the unit. If the unit is installed incorrectly, water leakage,
electric shock, or fire may result.
• F or installation work, follow the instructions in the installation manual and
use tools and pipe components specifically made for use with R410A refrig-
erant.
T he R410A refrigerant in the HFC system is pressurized 1.6 times the pres-
sure of usual refrigerants. If pipe components not designed for R410A refrig-
erant are used and the unit is not installed correctly, the pipes may burst and
cause damage or injuries. In addition, water leakage, electric shock, or fire
may result.
• When installing the unit, use appropriate protective equipment and tools for
safety. Failure to do so could cause injuries.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its weight.
If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.
• If the air conditioner is installed in a small room, measures must be taken
to prevent the refrigerant concentration in the room from exceeding the
safety limit in the event of refrigerant leakage. Consult a dealer regarding
the appropriate measures to prevent the allowable concentration from being
exceeded.
Should the refrigerant leak and cause the concentration limit to be exceeded,
hazards due to lack of oxygen in the room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual. The units must
be powered by dedicated power lines and the correct voltage and circuit
breakers must be used. Power lines with insufficient capacity or incorrect
electrical work may result in electric shock or fire.
1
For safe and correct use, read this manual and the indoor unit installation manual thoroughly before installing the air-conditioner unit.
(*1) at the
sc
(*1)"
sc
S
(MVA)
sc
2.00
2.28
5. Drainage piping work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
6. Electrical work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7. Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8. Special Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Grounding lead wire
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
After installation work has been completed, explain the "Safety Precautions" use,
and maintenance of the unit to the customer according to the information in the
Operation Manual and perform the test run to ensure normal operation. Both the
Installation Manual and Operation Manual must be given to the user for keeping.
These manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affixed to the main unit.
• Use C1220 copper phosphorus, for copper and copper alloy seamless pipes,
to connect the refrigerant pipes. If the pipes are not connected correctly, the
unit will not be properly grounded and electric shock may result.
• Use only specified cables for wiring. The wiring connections must be made
securely with no tension applied on the terminal connections. Also, never
splice the cables for wiring (unless otherwise indicated in this document).
Failure to observe these instructions may result in overheating or a fire.
• The terminal block cover panel of the outdoor unit must be firmly attached. If
the cover panel is mounted incorrectly and dust and moisture enter the unit,
electric shock or fire may result.
• The appliance shall be installed in accordance with national wiring regula-
tions.
• If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
• When installing or relocating, or servicing the air conditioner, use only the
specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it
with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high pres-
sure in the refrigerant line, and may result in an explosion and other hazards.
The use of any refrigerant other than that specified for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
• Do not perform pump down work when there is a gas leak. The intake of air
or other gases causes abnormally high pressure in the refrigeration cycle,
which may cause explosion or injury.