Functions Of Fcu Kit - Samsung DVM Installation Manual

Fcu application kit mim-f00n installation
Hide thumbs Also See for DVM:
Table of Contents

Advertisement

Functions of FCU KIT

y Fan control (Auto, High, Mid, Low), valve control, setting indoor temperature, sensing
y
inlet water pipe temperature is possible by FCU KIT. (Room temperature sensor must be
installed.)
y For direct power supply from FCU KIT, fan motor must work at AC 208 - 230 V~ 60 Hz,
y
AC 220 - 240 V~ 50 Hz and 1 A or low. Otherwise, install relay for external power suppy
to the fan motor.
y 2/3 way solenoid valve is a type that works at AC 208 - 230 V~ 60 Hz, AC 220 - 240 V~
y
50 Hz and supports product with 0.5 A or low.
Fan power
AC 208 - 230 V~ 60 Hz, 1 Ph, 1 A
AC 220 - 240 V~ 50 Hz, 1 Ph, 1 A
M
M
Water valve
AC 208 - 230 V~ 60 Hz, 1 Ph, 0.5 A
AC 220 - 240 V~ 50 Hz, 1 Ph, 0.5 A
OPTION FCU KIT_IBIM_06104A-00_EN.indd 19
Water-IN 1 sensor
Water-IN 2 sensor
CN4
CN4
F1
12V
F2
COMMON
LOW
MID
FAN
HIGH
Water Valve 1
Water Valve 2
ELCB
AC 208 - 230 V~ 60 Hz, 1 Ph
AC 220 - 240 V~ 50 Hz, 1 Ph
Room sensor (optional)
LED
Wireless signal
receiver
External
contact
F4
F3
19