FCU KIT installation
AC, FAN power
output cable
y Use conduit (1/2") and fitting (1/2") for power cable, and use cable gland (3/4") for DC
y
cables.
y Each parts must be certified by national authority.
y
– USA: UL certified products (UL514B), Europe: CE certified products
y Withdraw DC cables by spare holes if the DC cable wire holder is too tight.
y
y Use double-sheathed cables when using DC spare holes.
y
y Fix the power and communication cable at internal mount tie by using cable ties.
y
y Do not unscrew water valve cable wire holder if not used.
y
y Installation may be more simple by inserting sensor connector before connecting
y
communication cable.
NOTE
• Arrange communication cables (F1, F2, R1, R2) to the opposite way of power cable.
20
OPTION FCU KIT_IBIM_06104A-00_EN.indd 20
AC, water valve
AC, Power
power output
input cable
cable
y Power cable: Conduit and Conduit fitting (1/2") work by installer
y
y Water valve: Conduit and Conduit fitting (1/2") after separating
y
screw by installer when necessary
y DC, zero voltage contact: cable gland (3/4") work by installer
y
Spare holes (Use for DC cables)
DC Communication cable (F1, F2, R1, R2)
Room sensor (optional), Water sensor
Wired remote controller connection
2016-03-16 오후 2:44:41