Daikin DBC Series Installation Instructions Manual page 9

Light commercial packaged heating and cooling unit 7.5t to 12.5t
Hide thumbs Also See for DBC Series:
Table of Contents

Advertisement

POWER THRU THE CURB
NOTE: CHECK TRANSFORMER TO
MATCH THE CORRECT VOLTAGE TAP
WITH LINE VOLTAGE
control box
note: depending on the options installed, the
location of the components may vary in some
models.
Failure of unit due to operation on improper
line voltage or with excessive phase unbalance
constitutes product abuse and will void your
warranty and may cause severe damage to the
unit electrical components.
Areas Without Convenience Outlet
It is recommended that an independent 115V power source
be brought to the vicinity of the roof top unit for portable
lights and tools used by the service mechanic.
NOTE: Refer to local codes for requirements.
These outlets can also be factory installed.
LINE VOLTAGE L1, L2, L3
WARNING
Units installed on Roof Tops
Main power and low voltage wiring may enter the unit
through the condenser end of unit or through the roof curb.
Install conduit connectors at the desired entrance locations.
External connectors must be weatherproof. All holes in the
unit base must be sealed (including those around conduit
nuts) to prevent water leakage into building. All required
HIGH VOLTAGE BLOCK
conduit and fittings are to be field supplied.
Supply voltage to roof top unit must not vary by more than
10% of the value indicated on the unit data plate. Phase
CONTROL BOX
voltage unbalance must not exceed 2%. Contact your
local power company for correction of improper voltage or
phase unbalance.
LOW VOLTAGE ENTRANCE
SUPPLY
RETURN
electrical entrance and thru curb
Low Voltage Control Wiring
1. A 24V thermostat must be installed for unit operation.
2. Locate thermostat or remote sensor in the conditioned
space where it will sense average temperature. Do
not locate the device where it may be directly exposed
to supply air, sunlight or other sources of heat. Follow
installation instructions packaged with the thermostat.
3. Use #18 AWG wire for 24V control wiring runs not
exceeding 75 feet. Use #16 AWG wire for 24V control
wiring runs not exceeding 125 feet. Use #14 AWG
wire for 24V control wiring runs not exceeding 200
feet. Low voltage wiring may be National Electrical
Code (NEC) Class 2 where permitted by local codes.
9
20-3/4"
24.4"
SUPPLY
HIGH VOLTAGE ENTRANCE
(REMOVE PLUG)
RETURN
THRU THE CURB