1.0 Introduction The Impaq S is a wired shock sensor and the Impaq SC is a wired shock sensor with the option for a magnetic contact. Sections 1.1 and 1.2 show the key parts of the devices. 1.1 Impaq S...
Icon Item LED function select DIP switch Sensitivity selection button Magnet sensor Alarm resistance value selection DIP switch Tamper resistance value selection DIP switch Input terminal block 2.0 Mounting 2.1 Device mounting Select the intended mounting position. The device can be installed in any mounting orientation.
2.2 Magnet mounting (type SC only) Once the device has been mounted, position the magnet so the notch is aligned with the arrow marker on the PCB. The magnet can be installed on either side of the device. Greater sensitivity is achieved by positioning the magnet so the notch is aligned with the arrow (see figure 4 for magnet distances).
Page 11
Approach Min Removal Max Axis (mm) (mm) Right INS877-1 11/20...
Page 12
Left Once the correct position has been located fix the magnet in place (see figure 5) Figure 5 INS877-1 12/20...
This table is for the shock sensor only Cooper Panel Support Texecom Honeywell DSC Menvier Alarm EOL Tamper EOL Select the correct resistance value for Tamper and Alarm by moving the DIP switch to the ON position (Texecom values shown in example below). INS877-1 14/20...
Page 15
NOTE: The product will only function if both DIP switches have a single switch set to the ON position. If no switches or multiple switches are moved the product will not function as expected. INS877-1 15/20...
3.2 Connections Connect two wires into the 0V and 12V terminals to supply power to the device from an EN50131 compliant power supply unit. Connect two wires into the terminals marked EOL for the Alarm and Tamper signals. These wires should be terminated into a zone on the intruder panel. 3.3 Connections - Impaq SC only Connect two cores into the terminals marked MAG for the alarm signals from the magnetic contact.
NOTE: Any selections made on the comfort and detection LED switches will be overridden when the RLED function is utilised. 5.0 Setting the shock sensitivity After powering up the device single press the sensitivity button and the LED will flash blue defaulting to sensitivity setting 2. There are 5 sensitivity settings from 1 to 5 with 1 being the least sensitive (slowest flash rate) and 5 the most sensitive.
Recommended Sensitivity Setting* Material Radius Wood Framed Glass Window Concrete 0.5m Before testing the device, press and hold the button (3 secs) to set the desired sensitivity setting. The LED will turn green for confirmation at which point the device is ready for impact testing.
As the Impaq S/SC is not a complete alarm system, but only a part thereof, Texecom cannot accept responsibility or liability for any damages whatsoever based on a claim that the Impaq S/SC failed to function correctly. Due to our policy of continuous improvement Texecom reserves the right to change specification without prior notice.
Page 20
Certified by Telefication B.V. INS877-1 20/20...
Need help?
Do you have a question about the Impaq S and is the answer not in the manual?
Questions and answers