NetCol8000-A(050, 100) In-room Air Cooled Smart
Cooling Product
User Manual
●
●
●
2.2.3 Monitoring System
The monitoring system provides logic control, data collection, control delivering,
alarm reporting, data storage, user right management, and teamwork. It can
connect to your monitoring system over a northbound port (RS485) for remote
management.
The NetCol8000-A series products can be networked over a controller area
network (CAN) bus to perform the teamwork, which efficiently save energy and
prolongs the service life.
Figure 2-7
Figure 2-7 Network diagram for the monitoring system
2.2.4 Ports
The following table lists NetCol8000-A series product ports.
Table 2-3 Ports of the NetCol8000-A series product
Ports name
Liquid pipe of refrigerant
Discharge pipe of refrigerant
Condensate drainpipe
Water pipe inlet of the humidifier
Issue 12 (2020-10-28)
The fault diagnosis system automatically displays the information of the
current fault, which facilitates the maintenance.
The NetCol8000-A provides abundant external ports such as RS485 ports, fast
Ethernet (FE) ports, and USB ports that are protected by a security
mechanism.
The smart cooling product supports a maximum number of 500 alarms.
shows the networking diagram for the monitoring system.
Copyright © Huawei Technologies Co., Ltd.
2 Product Description
Specifications
Inside diameter 5/8 in. (15.9 mm)
Inside diameter 7/8 in. (22.3 mm)
BSPP 3/4 in.
BSPP 3/4 in.
19