AC filter operation is required only for the AC OUTPUT waterproof connector, not required for
other waterproof connectors.
Following are the reference torque values for the waterproof connector and tube. Observe the
requirements of the specific manufacturer, if any.
− AC OUTPUT and COM ports: 7.5 N· m (plastic) or 10 N· m (metal)
− RESERVE port: 3.75 N· m (plastic) or 6.25 N· m (metal)
1. Remove the AC filter and save the screws for later use.
2. Remove the cable gland and cap from the waterproof connector, and then remove the waterproof
connector.
3. Secure the tube fittings.
4. Install the AC filter in the original position.
AC filter
Routing Cables Through Waterproof Connectors (Using AC OUTPUT
4.3
as an Example)
NOTE
For ease of connecting the AC output power cable, you are advised to remove the nut assembly
from the AC terminal and save it for later use, and then route the cable through the waterproof
connector.