Download Print this page

Lutron Electronics DFCSJ-OEM-OCC Quick Start Manual

Clear connect wireless fixture controllers with occupancy sensor/rf only

Advertisement

Quick Links

Clear Connect Wireless Fixture
Controllers
Part of the Vive Family
041600
Please read before installing.
Rev. A
03/2017
DFCSJ-OEM-OCC
Clear Connect Wireless
Fixture Controller (with Occupancy Sensor)
DFCSJ-OEM-RF
9.5–20.5 V-
Clear Connect
80-250 mA
Wireless Fixture Controller (RF Only)
Clear Connect Wireless Fixture Controllers
UL 2043 Plenum Rated
Controls up to 4 ballasts or drivers (IEC 60929 Annex E.2 requires each ballast or
driver to limit the sink/source current draw to 2.0 mA maximum).
FCC information and IC information
This device complies with part 15 of the FCC Rules and Industry Canada
license-exempt RSS standard(s). Operation is subject to the following
two conditions: (1) This device may not cause interference, and (2) this
device must accept any interference, including interference that may
cause undesired operation. Modifications not expressly approved by
Lutron Electronics Co., Inc. could void the user's authority to operate this
equipment.
NOTE: This equipment has been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to
radio communications. However, there is no guarantee that interference
will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged
to try to correct the interference by one or more of the following
measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• C onnect the equipment into an outlet on a circuit different from that to
which the receiver is connected.
*
For set-up, programming, and
troubleshooting with a Vive system,
please refer to the installation
instructions included with the Vive hub
or at www.lutron.com
Important Notes:
• For installation by a qualified fixture manufacturer.
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 32 °F and 131 °F (0 °C and 55 °C), ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
• Sensor should be mounted to fixture in orientation that makes it parallel to
the floor when fixture is installed in ceiling.
Default Functionality
Fixture Controls
Auto On level: DFCSJ-OEM-OCC only
(not applicable for DFCSJ-OEM-VAC or DFCSJ-OEM-RF)
Varies with ambient light level when occupancy is triggered
(e.g., 100% for a dark room, 10% for a bright room).
Timeout period: 15 minutes
For more information, see
www.lutron.com/TechnicalDocumentLibrary/3691039.pdf
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Required Components
For each fixture, you will need:
Daylight
One Fixture Control
sensor lens
PIR lens
Button
OR
Clear Connect Wireless Fixture
Clear Connect Wireless Fixture
Controller (with Occupancy Sensor)
Controller (RF Only)
(DFCSJ-OEM-RF)
(DFCSJ-OEM-OCC)
Start Here
Install Clear Connect Wireless Fixture Controller
1
WARNING! Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
• E nsure knockout and adjacent surfaces are free from burrs, oil, chemicals, debris, etc.
• D o not push on the PIR lens or button to install the wireless fixture control. Push on the center of the
wireless fixture control.
Connector (poke-in style)
• 1 8 to 22 AWG (0.75 to 0.3 mm
) solid copper wire
2
• W ire strip length: 0.31 in (8 mm)
Mounting Thickness
Snaps enable mounting to the following material thickness ranges:
• 0 .04 in (1 mm) or less
• 0 .041 to 0.08 in (1.1 to 2 mm)
• 0 .081 to 0.13 in (2.1 to 3.3 mm)
0.041 to 0.08 in
0.04 in (1 mm)
(1.1 to 2 mm)
or less
Daylighting Sensor
D o not install in direct view of the light source or reflecting surface.
PIR Sensor
• I nstall in a location that allows the sensor to have an unobstructed view of the area.
• I nstall away from radiated heat given off by the light source.
Temperature
The wireless fixture control is rated for 55 °C (131 °F) maximum. Product must be installed in an area
that will not allow it to exceed this rating. Keep away from heat generating devices (e.g., drivers) and
verify during the fixture design process.
Release Wires from Connectors
Press connector buttons while pushing the wires slightly inward. Pull wires outward to release the wires from the
connectors. Do NOT pull out the wires without using the connector buttons, as damage to the product
can occur.
Connector buttons
Customer Assistance | 1.844.LUTRON1 USA, Canada, and the Caribbean | +44.(0)20.7702.0657 Europe | +1.610.282.3800 Others | www.lutron.com
Daylight
sensor lens
Button
Wiring Best Practices (for RF consideration)
• K eep all the fixture wiring to the minimum length needed to achieve the connections in an organized manner. Avoid unnecessary slack in the
wires.
• I f the driver is provided with a ground terminal, this terminal must be electrically connected to the grounded fixture metal using a ground wire
that is no longer than 2 in (51 mm).
• M echanically affix all the wires to the fixture wall so that they are kept as close possible to the grounded fixture metal.
• E nsure that the driver wiring is as far as possible from the wiring immediately connected to the wireless fixture control
• E nsure that the wireless fixture control is mounted away from the LED strips to minimize the coupling of the RF radiation from the LED strips
into the wireless fixture control.
• F or more information, see www.lutron.com/TechnicalDocumentLibrary/048620.pdf
Wireless fixture controller (RF only)
• T he Wireless fixture controller (RF only) (DFCSJ-OEM-RF) can be installed on the back of the fixture, assuming metal tiles are not being used.
• T he Wireless fixture controller (RF only) will be rated for use in plenum areas.
• D o not fully enclose within the metal fixture.
Mounting to Curved Surfaces
Mounting directly to a curved surface is not recommended. An adaptor (custom manufactured by the OEM) may be required to ensure that
the device is seated properly.
Remote Mounting
The wireless fixture control is intended for troffer and linear fixtures and is not intended to be ceiling mounted.
0.081 to 0.13 in
Wiring Diagrams
(2.1 to 3.3 mm)
120 – 277 V~
Clear Connect Wireless Fixture Controllers with
Ecosystem or DALI Driver
120 – 277 V~
Wireless Fixture Control with Driver with
Self-powered DALI Link
Packaging
Fixture packaging must protect the installed wireless fixture control so that it does not get damaged in shipping.
At least one EcoSystem driver + Wireless Sensor Interface (PS-OEM-2W-UNV)
EcoSystem driver
+
Or
At least one driver with self-powered DALI link
Driver with self-powered DALI link
N
L
S+
S-
Wireless sensor interface
E+
Clear Connect Wireless
E-
Fixture Controller
E1
E2
Driver with self-powered DALI link
Clear Connect Wireless
Fixture Controller
Wireless sensor interface
EcoSystem / DALI driver
120 – 277 V~

Advertisement

loading

Summary of Contents for Lutron Electronics DFCSJ-OEM-OCC

  • Page 1 Do NOT pull out the wires without using the connector buttons, as damage to the product (not applicable for DFCSJ-OEM-VAC or DFCSJ-OEM-RF) can occur. Connector buttons Varies with ambient light level when occupancy is triggered (e.g., 100% for a dark room, 10% for a bright room). Timeout period: 15 minutes For more information, see www.lutron.com/TechnicalDocumentLibrary/3691039.pdf Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 USA...
  • Page 2 Note: Any associations or programming previously set up 3. C over daylight lens/button with opaque material. Fixture light will with the fi xture control will be erased and will need to be dim up over 1 minute (hold opaque material steadily in place) re-programmed. Lutron, Pico, PowPak, EcoSystem, and Energi TriPak are trademarks of Lutron Electronics Co., Inc. registered in the U.S. and other countries. Radio Powr Savr and Vive are trademarks of Lutron Electronics Co., Inc. Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. 7200 Suter Road ©2017 Lutron Electronics Co., Inc. Coopersburg, PA 18036-1299 USA...

This manual is also suitable for:

Dfcsj-oem-rf