G
-
®
ECO
Tec
AS
FIRED WATER BOILER
Wall-mounting the boiler
(continued)
Boiler mounting bracket
The jacket door can be left in place when
handling the boiler, but the boiler must ONLY
be lifted by the bottom and rear of the sheet
metal housing — NOT by any pipe or plastic
part.
3.
4. Lift the boiler high enough that its mounting bracket
(Figure 6, Item 3) will be above the wall-mount bracket
(Figure 5, page 10, Item 2).
5. Let the rear of the boiler slide against the wall bracket as
you lower the boiler into place.
6. Adjust the boiler properly until engaged with the wall
bracket and the boiler slips into the correct position.
7. When the brackets are engaged correctly, the bottom of
the boiler enclosure will be at or near the pencil line, or
tape, you applied in step 2.
When mounting the boiler, use the method
described on step 2, page 10 to ensure the
boiler bracket and the wall bracket are properly
engaged. If not, the boiler could fall. Failure to
comply could result in severe personal injury,
death or substantial property damage.
8. Ensure boiler is level front-to-back.
Ensure boiler is NOT pitched downward
with the front of the boiler lower than
the back of the boiler. This can prevent
condensate from draining properly. Failure
to comply could result in severe personal
injury, death or substantial property damage.
Part number 550-100-260/0520
80/110/150/199
Pedestal floor stand assembly
Pedestal floor stand
1. Carefully remove boiler from the styrofoam protective base and
set on back. Remove door from front of boiler by unfastening
latches on side of cabinet.
2. Remove four (4) 5/16" studs from floor stand hardware trim
bag. Install studs by hand in rivet nuts on bottom of boiler.
See Figure 7.
3. Remove front access panel from pedestal assembly by sliding
it up.
4. Align holes in top of pedestal with studs on bottom of boiler.
Slide stand over studs. Remove 5/16" nuts from trim bag.
Install nuts on studs using ½" socket or wrench. Make sure
to align sides of pedestal with cabinet before tightening down
nuts. Do not overtighten.
5. Install the condensate trap assembly following instructions
on page 56
6. After confirming nuts are tightened, obtain assistance and lift
the boiler into upright position.
.
7. Set boiler in place and level by adjusting leveling legs with
flat head screwdriver.
Pedestal floor stand assembly (front access