How To Attach The Ring Pressure Terminal; Connecting Wiring; Connecting To External Equipment - Panasonic CZ-CFUSCC1 Installation Instructions Manual

Cloud adaptor
Hide thumbs Also See for CZ-CFUSCC1:
Table of Contents

Advertisement

Wiring
(continued)
Before connecting the wiring, be sure to turn the circuit breaker off. After all wiring arrangements are complete, turn the circuit breaker on.
If the power supply wiring is mistakenly connected to a terminal board other than the power supply terminal board, the devices to
be connected to this controller or this controller will malfunction. After connecting the wiring, confi rm that the power supply wiring is
properly connected.
 How to Attach the Ring
Pressure Terminal
 For power supply wiring
• Process the end of each wiring, and attach
the ring pressure terminal (fi eld supplied
item).
Ring
pressure
Strip
terminal
 For shield wiring
• Process the end of the each wiring, and
attach the ring pressure terminal (fi eld
supplied item).
Remove wiring coat.
1
Shield mesh
Cover with the tape.
2
Insulation
tape
Attach ring pressure terminal.
3
Attention
• Ground the shield on both sides of shield
wiring, otherwise an operation error from noise
may occur.
shield wiring
Ground

Connecting to External Equipment

 Outputs of Pulse meter (Gas meter, Power meter and Heat meter) can be input to signal terminal board.
 Keep the external I/O wiring lengths of 20 meters or less. If a longer length is needed, use a relay.
Controller side
Condition
Non-voltage contact "a" Pulse
• Contact allowable voltage :
DC5 V±10 %
• Contact allowable current :
Max. 10 mA
 Connecting Wiring
• When connecting external equipment, refer to the "Connecting to external
equipment" section below.
Power supply
wiring
Inter-unit
control wiring
Strip
Shield
mesh
Use this screw when connecting the shield
for the inter-unit control wiring to ground. (FG*)
*: Functional Ground
• Do not run the inter-unit control wiring through the same conduit as the power supply
wiring, or run close to the power supply wiring (maintain at least 30 cm separation).
• Use different inter-unit control wiring and power supply wiring so they can be
differentiated visually.
Ground
External equipment side
Terminal name
Terminal
Common (COM)
7
Pulse input 1 (Pi1)
8
Pulse input 2 (Pi2)
9
Pulse input 3 (Pi3)
10
L
N
Connect to inter-unit control wiring (LINK1)
Connect to inter-unit control wiring (LINK2)
Circuit
Condition
example
• Pulse width :
COM
30 msec or
more / 100
msec or more
• Pulse interval :
1 sec or more
4
Power supply terminal board (TB1)
Power switch
TB1
ON
OFF
The earth wiring for protection should be longer than
the power line (L, N).
Fix the wiring by using the clamper.
TB2
U1
U2
U1
U2
Signal terminal board (TB2)
0
1
2
3
4
5
Pulse Input
6
Common (COM)
7
Pulse input 1 (Pi1)
8
Pulse input 2 (Pi2)
9
Pulse input 3 (Pi3)
10
11
12
13
LAN cable
LAN terminal
Signal
terminal
board (TB2)