Commissioning
10.1

Preparations

10-2
PSI 6XXX.190 W1
Connect and turn on the timer according to the wiring diagrams and safety instruc-
D
tions.
Deactivate the <Weld external> signal for as long as you do not need any welding
D
current for commissioning.
Start the BOS-5000 software and enter your user group and user password.
D
Select Operation.
D
Check in the plant layout whether there is a link (V24 -> timer or field bus interface
D
board -> timer) between the programming terminal and the timer.
-
If the timer is not linked to the programming terminal (gray timer symbol in
plant layout), check the connection cable or the address settings (with Profi-
bus installations, also check the circuitry of the terminating resistors), the
Timer Reference and the power supply to the timers.
Select the timer and program for commissioning in the BOS-5000 software.
D