Vacuum Pumping And Leak Detection - Gree GWH09AEC-K6DNA1A Series Service Manual

Refrigerant r32
Hide thumbs Also See for GWH09AEC-K6DNA1A Series:
Table of Contents

Advertisement

(2) Fix the power connection wire and power cord with wire clip.
Note:
(1) After tightening the screw, pull the power cord slightly to
check if it is firm.
(2) Never cut the power connection wire to prolong or shorten
the distance.
6. Neaten the Pipes
(1) The pipes should be placed along the wall, bent reasonably
and hidden possibly. Min. semidiameter of bending the pipe is
10cm.
(2) If the outdoor unit is higher than the wall hole, you must set
a U-shaped curve in the pipe before pipe goes into the room,
in order to prevent rain from getting into the room.(As show in
Fig.24)
Wall
U-shaped curve
Drain hose
Fig.24
Note:
(1) The through-wall height of drain hose shouldnt be higher
than the outlet pipe hole of indoor unit.(As show in Fig.25)
(2) Slant the drain hose slightly downwards. The drain hose
cant be curved, raised and fluctuant, etc.(As show in Fig.26)
(3) The water outlet cant be placed in water in order to drain
smoothly.(As show in Fig.27)
The drain hose can't be fluctuant
The drain hose
can't be fluctuant
The water
outlet can't be
fluctuant
Fig.26
8.7 Vacuum Pumping and Leak
Detection
1. Use Vacuum Pump
(1) Remove the valve caps on the liquid valve and gas valve
and the nut of refrigerant charging vent.
(2) Connect the charging hose of piezometer to the refrigerant
charging vent of gas valve and then connect the other charging
hose to the vacuum pump.
(3) Open the piezometer completely and operate for 10-15min
to check if the pressure of piezometer remains in -0.1MPa.
38
The drain hos
can't raise
upwards
Fig.25
The water outlet
can't be placed
in water
Fig.27
(4) Close the vacuum pump and maintain this status for 1-2min
to check if the pressure of piezometer remains in -0.1MPa. If
the pressure decreases, there may be leakage.
(5) Remove the piezometer, open the valve core of liquid valve
and gas valve completely with inner hexagon spanner.
(6) Tighten the screw caps of valves and refrigerant charging
vent.(As show in Fig.28)
Liquid valve
Gas valve
Refrigerant charging
vent
Nut of refrigerant
Charging vent
Fig.28
2. Leakage Detection
(1) With leakage detector:
Check if there is leakage with leakage detector.
(2) With soap water:
If leakage detector is not available, please use soap water for
leakage detection. Apply soap water at the suspected position
and keep the soap water for more than 3min. If there are air
bubbles coming out of this position, theres a leakage.
Service Manual
Piezometer
Lo
Hi
Valve cap
Vacuum pump
Inner hexagon
spanner
Close
Open
Installation and Maintenance