Mitsubishi Electric City Multi PLFY-P VEM-E Series Installation Manual page 10

Air conditioners for building application, indoor unit

Advertisement

(slide switch). Select a suitable setting from the table below according to the instal-
lation location.
SW21-1
SW21-3
OFF
4 direction
SW21-4
ON
SW21-3
OFF
3 direction
SW21-4
OFF
SW21-3
ON
2 direction
SW21-4
OFF
If you want to sense room temperature with the built-in sensor in a remote control-
ler, set SW1-1 on the control board to "ON". The setting of SW1-7 and SW1-8 as
thermometer is OFF.
Model
PLFY-P20VEM-E
PLFY-P25VEM-E
PLFY-P32VEM-E
PLFY-P40VEM-E
PLFY-P50VEM-E
PLFY-P63VEM-E
PLFY-P80VEM-E
PLFY-P100VEM-E
PLFY-P125VEM-E
PLFY-P20-P80VEM
Silent
Standard
SW21-2
SW21-1
SW21-2
OFF
ON
OFF
OFF
2.5 m
2.7 m
2.7 m
3.0 m
3.0 m
3.3 m
Power supply
Max.: 264V
Min.: 198V
Note:
High ceiling
Silent
SW21-1
SW21-2
SW21-1
SW21-2
ON
OFF
OFF
3.5 m
2.7 m
3.5 m
3.0 m
3.5 m
3.3 m
Symbols: MCA: Max. Circuit Amps (= 1.25×FLA)
IFM: Indoor Fan Motor
MCA (A)
0.28
0.28
0.28
0.36
0.36
0.45
0.64
1.25
1.34
PLFY-P100-P125VEM
Standard
High ceiling
SW21-1
SW21-2
SW21-1
ON
OFF
OFF
ON
3.2 m
3.6 m
4.0 m
FLA: Full Load Amps
Output: Fan motor rated output
IFM
Output (kW)
FLA (A)
0.05
0.05
0.05
0.05
0.05
0.05
0.05
0.12
0.12
SW21-2
OFF
4.5 m
4.5 m
4.5 m
0.22
0.22
0.22
0.29
0.29
0.36
0.51
1.00
1.07