Section 3 Configuration

Controller IP Addresses

Before a redundant hardware installation you have to concider the following.
Remember that the Backup controller IP Addresses must be set in the primary
Processor Unit. This can only be done though the IPConfig tool.
There are three alternatives:
Use Default rule if not in conflict with any other IP-address on the network.
In the case you need to set an IP address to a redundant CPU, the backup CPU needs
to be turned off (powered down). Otherwise the backup CPU takes over and you
will not be connected.

Setting CPU as Redundant in Control Builder M

The redundant PM861/PM864 must be set as redundant in the Control Builder M
Project Explorer. Also see Hardware Configuration and Redundancy in the
Control Builder M online help.
3BSE 027 941 R301
Disable interface.
Use default rule.
Specify an address of your own.
Controller IP Addresses
95