Fault-Finding Procedures

8.
Fault-Finding Procedures

PM8xx Processor Unit

F(ault) LED is ON
R(un) LED is OFF
B(attery) LED is flashing
128
Check that the relevant LED lights up.
Table 21. PM8xx – Fault-Finding Procedure
Fault
Possible Cause and Corrective Action
Controller Re-start, (INIT), in progress.
Wait for Controller restart to finalize.
If condition persists:
Check the CEX-bus fuse.
Check for a unit failure on the CEX-bus.
See Fault-Finding,
Table 25
on page 131,
Table 27
on page 135 and
138.
No application loaded on the Controller.
Load application.
Restart Controller (INIT push button).
Controller application failed.
Reload application.
Restart Controller (INIT push button).
Battery power (Internal or External) is below an
acceptable level or non-existent.
Install new battery.
External battery cable disconnected.
Connect external battery cable.
See Fault-Finding
Table 23
Section 5 Maintenance
Table 24
on page 130,
Table 26
on page 134,
Table 30
on page
on page 129.