Fault-Finding Procedures
8.
Fault-Finding Procedures
PM8xx Processor Unit
F(ault) LED is ON
R(un) LED is OFF
B(attery) LED is flashing
128
Check that the relevant LED lights up.
Table 21. PM8xx – Fault-Finding Procedure
Fault
Possible Cause and Corrective Action
Controller Re-start, (INIT), in progress.
•
Wait for Controller restart to finalize.
If condition persists:
•
Check the CEX-bus fuse.
•
Check for a unit failure on the CEX-bus.
See Fault-Finding,
Table 25
on page 131,
Table 27
on page 135 and
138.
No application loaded on the Controller.
•
Load application.
•
Restart Controller (INIT push button).
Controller application failed.
•
Reload application.
•
Restart Controller (INIT push button).
Battery power (Internal or External) is below an
acceptable level or non-existent.
•
Install new battery.
External battery cable disconnected.
•
Connect external battery cable.
See Fault-Finding
Table 23
Section 5 Maintenance
Table 24
on page 130,
Table 26
on page 134,
Table 30
on page
on page 129.
3BSE 027 941 R301