Watts Aerco Benchmark 5000 Reference Manual page 68

With edge i controller
Hide thumbs Also See for Aerco Benchmark 5000:
Table of Contents

Advertisement

Benchmark with Edge [I] Controller: Reference Manual
SECTION 6: BENCHMARK 5000 & 6000 PART LIST
Benchmark 5000-6000 Valve Proving System
P/N 24655 rev C – 8/23/2018
Item Qty Part #
1
1
24629-5
2
1
33261
RED ALARM LIGHT &
RESET SWITCH
1. OFF during normal
operation
2. ON indicates a leak
or Actuator failure
The Benchmark gas train P/N 22330-2 operates in conjunction with a Valve Proving System,
P/N 24655. This system monitors the gas pressure on both sides of the Actuator. If the pressure
difference falls below a fixed value, indicating the failure of the Actuator or leakage in the gas
line, it triggers the shutdown of the boiler.
Once the problem has been diagnosed and corrected, the Valve Proving System must be reset
by pressing the red Reset switch before the unit is restarted.
OMM-0146_A • GF-219 • 5/25/2020
Description
Valve Proving System Assy.
Bracket, VPS Support
YELLOW RUN LIGHT
1. OFF during normal operation
2. ON during valve proving operation
3. ON when unit is not running
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
Item Qty Part #
Description
6
1
97087-48
Flexible Gas Tube (NOT SHOWN)
7
1
97087-26
Flexible Gas Tube (NOT SHOWN)
1
2
Page 68 of 76

Hide quick links: