Download Print this page

Delta DT-2000 Series Operation Manual page 3

Fire shutter motorised operator

Advertisement

Operation Manual- DT2000
1. Technical Parameters
1.1 Power Supply
Incoming power supply: 3 Phase 400V AC, 50Hz
1.2 Max Motor Power: 1500W
1.3 Feedback (BMS) & Fire Alarm Signal Contact Capacity: 24V DC, 500mA
1.4 Working Environment:
Temperature
Relative humidity
Atmospheric pressure
1.5 General Specification Table
Power
Torque
Rated Voltage
Phase
Frequency
Starting Current
Full Load Current
Starting Method
Pole
Rated Duration
Insulation Class
Drive Chain Size*
Output Sprocket*
Output Speed
Mounting
Manual Override
Thermal Protection
Controls
Controlled Descend
Thermal Release
Fire Alarm Input
BMS Feedback
Delay Descend
Backup Battery
Weight
Motor IP Rating
Motor Coating
Control Box IP Rating
Control Box Coating
: 0°C to 55°C
: ≤95%
: 85kPa to 106kPa
Model
Brake release with spring clutch
12V DC, 8Ah for brake release only
DT-2000
1500W
400Nm
AC 400V
3
50Hz
12A
3A
Direct on line
4
10min
F
#80
10T
24rpm
Straight 4 holes flange
Rotation Crank
Fan cooled with cooling fins
External PCB IC control box
Glass bulb/Fusible link
24V DC/Dry contact
Fully open, Fully close, Error
15sec
46kg
IP44B
HVLP Spray Coated
IP30
Powder Coated
Page 2 of 8

Advertisement

loading