Location and Function of the Interface Elements
A3
A1
A2
A7
A9
A8
A1
Type label (with space for physical address of the ac-
tuator)
A2
Identification number of the device
A3
Protective lid over bus connection
A4
Bus connection terminal block for single core conduc-
tors with 0.6...0.8 mm Ø
A5
LED for indicating normal operating mode (LED off) or
addressing mode (LED on); returns to normal operating
mode automatically after receiving the physical address
A6
Learning button for switching between normal operat-
ing mode and addressing mode and for receiving the
physical address
A7
1/2 inch screw nut
A8
Wire (red) Load A
A9
Wire (black) Line (Hot)
A10 Wire (grey) DIM Common
A11 Wire (purple) DIM A
(AWG # 18)
Dimension Diagram
Dimensions in mm (inch)
(3.54)
(2.76)
A4
A5
A6
A7
A3
A7
A10
A11
B1
4" x 4" Junction Box
B2
Device
B3
Bus connection pins of the module for connection of
the bus terminal block for single core conductors with
0.6...0.8 mm Ø
B4
1/2 inch screw nut
Mounting and Dismounting
∂ Mounting of a JB module:
(AWG # 12)
Option 1 (mounting inside a J-Box)
(AWG # 12)
- Insert the thread of the JB module (B2) into the 1/2 inch
(AWG # 18)
knockout between two adjacent J-Boxes (B1)
- Fasten the JB module (B2) with the 1/2 inch thread nut (B4)
- Remove the protective lid (B3) and connect the bus wire to
the bus terminal block (A4)
- Connect the wires from the device to the field wires using
wire nuts (not provided in package)
Option 2 (mounting outside of a J-Box)
- Insert the thread of the JB module (B2) into the 1/2 inch
knockout of the J-Box (B1)
- Fasten the JB module (B2) with the 1/2 inch thread nut (B4)
to the J-Box (B1)
- Connect the bus wire to the bus terminal block under the
protective cover (B3)
- Connect the wires from the device to the field wires using
wire nuts (not provided in package)
∂ Assignment of the Physical Address:
.
(1.76)
- A short push (< 2 s) of learning button (A6) enables the ad-
dressing mode, which is indicated when the LED is continu-
ously on (A5). The device returns to normal operating mode
(LED Off) automatically after receiving the physical address
or if the learning button is pushed again.
- A very long push (> 20 s) of the learning button resets the
device to factory settings. This is indicated by constant flash-
(2.76)
ing for 8 seconds.
- A long push (> 5 s up to 20 s) of the learning button ena-
bles the Connection Test for commissioning with Desigo.
This mode can be disabled by a short push any time.
- Install the protective lid (B3) and fasten with screws (pro-
vided in package)
∂ Dismounting a JB module:
- Disconnect power to the module
- Remove the wire nuts and bus connection
- Unfasten the 1/2 inch thread nut (B4) connecting the JB
module (B2) to the J-Box (B1)
- Remove the JB module (B2) from the J-Box (B1)
USA
Hazardous voltage.
Can cause death, or serious injury or property damage.
The device must not be opened.
A faulty device should be returned to the local Siemens sales office
or distributor.
The device must be mounted and commissioned by a factory trained person.
The prevailing safety rules must be observed!
Mount in dry locations only!
B2
B1
B4
B1
B3
B1
B4
B2
B3
instabus
Technical Manual
®
Switch-/Dimming Actuator
JB 527C23
5WG1 527-4CB23
April 2017 / Page 2
WARNING
WARNING
25...35 mm
5 mm
C2
C2.3
D2
D2.4
C2.2
C2.1
Wiring
Bus connection
Slipping off/on bus connection blocks
The bus connection block consists of two components (C2.1
and C2.2) with four terminal contacts each. Take care not to
damage the two test sockets (C2.3) by accidentally connect-
ing them to the bus cable or with the screw driver (e.g.
when attempting to unplug the bus connection block).
Slipping off bus connection blocks
- Carefully put the screw driver to the wire insertion slit of
the bus connection block's grey component (C2.2)
and
- pull the bus connection block (C2) from the module.
Note
Don't try to remove the bus connection block from the bot-
tom side. There is a risk of shorting-out the device!
Slipping on bus connection blocks
- Slip the bus connection block (C2) onto the guide slot of
the module and
- press the bus connection block (C2) down to the stop.
Connecting and Disconnecting bus cables
Connecting bus cables
- The bus connection block (D2) can be used with single
core conductors Ø 0.6...0.8 mm.
- Remove approx. 5 mm of insulation from the conductor
(D1) and plug it into the bus connection block (D2)
(red = +, grey = -)
Disconnecting bus cables
- Unplug the bus connection block (D2) and remove the
bus cable conductor (D1) while simultaneously wiggling
it.
Connecting mains and load circuit:
Connect wires
-
Connect wire leads using wire nuts.
L1V30425161A - DS02
D1
D2
D2.4