Download Print this page

HORNER APG SmartMod HE359DIQ512 Step-By-Step Manual page 9

Setting up and connecting to an xlt mj2 port

Advertisement

MAN0922-01-EN
17. If communications is established then the green Power LED on the front of the
HE359DIQ512 will flash (may not be visible at higher baud rates) and the XLt
screen will display a binary sequence of 0's and 1's in the first data field
'40006(SmartMod)' and a decimal value of between 1 and 247 in the second
data field '40007 (SmartMod)'.
18. Take note of the value displayed at 40006 and compare it to the following table
(Fig. 11) to discern the actual communication settings in the unit.
19. For example, a displayed value of: 0000000001011111 would indicate the
following: Bits 0-2 added to give Baud Rate:
The sum of these three bits gives a value of 7 indicating a Baud Rate of 38400
The sum of these two bits gives a value of 1 indicating Even Parity
Bits 7-15 are unused.
20. The second data field, 40007 will indicate the Node ID of the attached
SmartMod.
____________________________________________________________________________________
Page 9 of 14
Fig. 11
Bit 0 On = decimal 1
Bit 1 On = decimal 2
Bit 2 On = decimal 4
Bit 3 On = 8 Data Bits
Bit 4 On = decimal 1
Bit 5 Off = decimal 0
Bit 6 On = Modbus RTU Mode
SmarMod Quick Start Guide
1017

Advertisement

loading