HORNER APG SmartMod HE359DIQ512 Step-By-Step Manual

Setting up and connecting to an xlt mj2 port

Advertisement

Quick Links

Introduction to SmartMod
Step by Step Guide 1
Setting up and connecting an
HE359DIQ512 to an XLt MJ2 port

Advertisement

loading

Summary of Contents for HORNER APG SmartMod HE359DIQ512

  • Page 1 Introduction to SmartMod Step by Step Guide 1 Setting up and connecting an HE359DIQ512 to an XLt MJ2 port...
  • Page 2 MAN0922-01-EN SmarMod Quick Start Guide Cscape: 1. Open Cscape and create a new program file. 2. Select: Program/Protocol Configuration (Fig.1) Fig.1 3. Select Modbus Master protocol from the dropdown list (Fig.2) Fig.2 ____________________________________________________________________________________ Page 2 of 14 1017...
  • Page 3 MAN0922-01-EN SmarMod Quick Start Guide 4. Select Network button and setup (Fig.3). Fig.3 5. Select Ok and then Select Device button ____________________________________________________________________________________ Page 3 of 14 1017...
  • Page 4 MAN0922-01-EN SmarMod Quick Start Guide 6. Setup the device (Fig.4). Fig.4 1. A descriptive name for the attached device 2. Modbus ID for Smartmod. 1 is correct for initial communication 3. 5-digit Addressing for SmartMod 4. Enabling the Status register provides feedback (see troubleshooting the connection below).
  • Page 5 MAN0922-01-EN SmarMod Quick Start Guide 8. Click Add and setup (Fig. 5). Fig. 5 1. Select device from drop down list. Bracketed number indicates Node 2. Starting register. (Holding registers are appropriate) 3. Up to 8 registers are required for the HE359DIQ512 4.
  • Page 6 MAN0922-01-EN SmarMod Quick Start Guide 10. Select Screens/View edit Screens (Figs. 6&7). Fig.6 ____________________________________________________________________________________ Page 6 of 14 1017...
  • Page 7 MAN0922-01-EN SmarMod Quick Start Guide Fig.7 11. Select Numeric Data button then click and drag an area on the XLt screen. Double click the field and set up the data (Fig.8) Fig.8 12. Add a second similar data field to the screen. Use Controller Register %R0007 (40007 SmartMod) and use 3 digits, Decimal Format/Editable (Fig.
  • Page 8 MAN0922-01-EN SmarMod Quick Start Guide 14. Assemble the communications cable. Port details as per Fig 10. Note: These are the onboard MJ2 connections and not the cable connector. Fig.10 Connect: XLt MJ2 port (Half Duplex Mode) SmartMod Comm. Port Pin 1 (Tx+/Rx+) B (D+) Pin 2 (Tx-/Rx-) A (D-)
  • Page 9 MAN0922-01-EN SmarMod Quick Start Guide 17. If communications is established then the green Power LED on the front of the HE359DIQ512 will flash (may not be visible at higher baud rates) and the XLt screen will display a binary sequence of 0’s and 1’s in the first data field ’40006(SmartMod)’...
  • Page 10 MAN0922-01-EN SmarMod Quick Start Guide 21. Using the XLt touchscreen/keypad, edit the fields to suitable values for your application. 22. Any changes that are made to the SmartMod settings MUST also be reflected in the Cscape/XLt setup. Otherwise communications may be lost when the INIT to GND connection is disconnected and the SmartMod reset.
  • Page 11: Troubleshooting The Connection

    MAN0922-01-EN SmarMod Quick Start Guide TROUBLESHOOTING THE CONNECTION 1. There are several status registers that can be assigned to give an indication of the health of the Network and of individual Modbus Nodes (SmartMods) 2. In Cscape/Protocol Configuration/Network settings, assign a register as in Fig.
  • Page 12 MAN0922-01-EN SmarMod Quick Start Guide 3. If communications is established and good then expect to see the value in %R1006(7) increase. 4. If communications is established and bad then expect to see the value in %R1004(5) increase. Check the cable connections and or register addressing in Cscape/Protocol Configuratiuon/Scanlist 5.
  • Page 13 MAN0922-01-EN SmarMod Quick Start Guide 7. This register value gives feedback for the specific Modbus Node. • 129 - Slave Timeout • 130 - Bad Checksum (corrupted incoming data) • 131 - No response • 197 - Slave does not support this function. •...
  • Page 14 MAN0922-01-EN SmarMod Quick Start Guide Other Checks SmartMod PWR LED Off Check power to SmartMod SmartMod PWR LED not flashing Has communication been established? Is the Baud rate set for 9600 or lower? Cannot edit data on Xlt screen Ensure Editable box is ticked for Data Field.