HORNER APG SmartMod HE359DIQ512 Step-By-Step Manual page 8

Setting up and connecting to an xlt mj2 port

Advertisement

MAN0922-01-EN
14. Assemble the communications cable. Port details as per Fig 10.
Note: These are the onboard
MJ2 connections and not
the cable connector.
Connect:
XLt MJ2 port (Half Duplex Mode)
Pin 1 (Tx+/Rx+)
Pin 2 (Tx-/Rx-)
Pin 6 (0V)
For Initialisation settings connect:
SmartMod Comm. Port
15. When the cable is assembled connect the RJ45 end to MJ2 on the XLt. Connect
the Smartmod 4-way terminal block to the HE359DIQ512 comm. port.
16. Power-up the HE359DIQ512 SmartMod. The Initialisation settings (INIT
connected to GND at power-up) will cause the SmartMod to start in the following
mode: Baud Rate 9600, No parity, 1 Stop Bit and as Modbus Node ID 1. This
is to allow communications so the SmartMod can be configured for alternative
settings, if necessary. See Fig. 3 above for Cscape/XLt equivalent settings.
____________________________________________________________________________________
Page 8 of 14
C(GND)
Fig.10
SmartMod Comm. Port
B (D+)
A (D-)
C (GND)
SmartMod Comm. Port
D(INIT)
SmarMod Quick Start Guide