Download Print this page

Danfoss VLT DriveMotor FCM 300 Quick Setup page 2

Hide thumbs Also See for VLT DriveMotor FCM 300:

Advertisement

Factory setting
Reset (pushbutton)
Start
Jog
Speed reference
- Reset to be closed short time for
resetting fault trips
- Start to be closed for changing
to run mode
- Jog will run at fixed speed
while closed (10 Hz)
- Speed reference (0-10 V)
determines speed while in run mode
Fig. 1
Fig. 1
Fig. 1
Fig. 1
Fig. 1
The control cables must be screened cables.
Fig. 2
Fig. 2
Fig. 2
Fig. 2
Fig. 2
X100: Terminal block for data communication
Terminal
Function
No.
1
P RS 485
for connection to
2
N RS 485
bus or PC
3
5 V DC
Supply for RS 485 bus
4
0 V DC
T T T T T able A
able A
able A
able A
able A
X101: Terminal block for analog/digital control signals
Terminal
Function
No.
1
Analog input (0-20 mA)
2
Analog (0-10 V)/digital input 2
3
Digital input (or pulse) 3
4
Digital input (or precise stop) 4
5
Digital input (other) 5
6
24 V DC supply for digital inputs (max. 50 mA)
7
10 V DC supply for potentiometer (max. 15 mA)
8
0 V for terminals 1-7 and 9
9
Analog (0-20 mA)/digital output
T T T T T able B
able B
able B
able B
able B
02/00
VL
VLT T T T T
VL
VL
VL
This Quick Setup gives information on safety and
helps you to get your FCM 300 Series motors
installed and running in factory setting, see fig. 1. For
additional information, please see the Design Guide.
Before you start, please read the safety instructions
on the back of this Quick Setup.
Mechanical installation
Mechanical installation
Mechanical installation
Mechanical installation
Mechanical installation
Terminals
Install the FC motor with adequate access for routine
1: Analogue input
maintenance. Adequate space, particularly at the fan
inlet (50 mm), is necessary to facilitate airflow.
2: Analogue input
3: Digital input
Where several FC motors are installed in close
4: Digital input
proximity, care must be taken to ensure that there is
5: Digital input
no recirculation of exhausted warm air.
6: 24 V DC supply
NB!
NB!
NB!
NB!
NB!
7: 10 V DC supply
8: 0 V
9: Output
to exceed 35 °C. If the ambient temperature is in the
range of 40 °C - 55 °C, a reduction of the service life
of the FC part is to be expected. For further
information, please see the section on derating in the
Design Guide.
Electrical connections
Electrical connections
Electrical connections
Electrical connections
Electrical connections
Remove the inverter box cover, which is held by four
screws, to obtain access to the terminals.
Remove the detachable terminal plugs from the
terminal blocks X100 and X101 to obtain access to
the mains terminals.
Lift only the corner of the black plastic cover by the
cable entries to expose the mains terminals L
and L
NB!
NB!
NB!
NB!
NB!
Do not lift or remove the entire plastic cover. The
NB!
NB!
NB!
NB!
NB!
Mains terminals L
Connect the three mains phases to terminals L
and L
provided.
T T T T T ightening T
ightening Tor or or or orques
ightening T
ightening T
ightening T
L1, L2, L3
L1, L2, L3
Earth ground FCM 305-375
Example
Another direction of rotation can be programmed,
see the Design Guide.
Feedback
signal
Speed
reference
Start the FC motor
Start the FC motor
Start the FC motor
Start the FC motor
Start the FC motor
Reset
Connect mains. LED 302 (green) lights up to indicate
Start
that the power is on. In Profibus versions, LED 303
Jog (fixed
will flash. For further information on Profibus, please
speed)
see the Profibus manual.
Connect terminal 4 and 6 to the start button (see fig.
1).
Fault
Connect terminal 2, 7 and 8 to the potentiometer
indication
(see fig. 1).
Mount the inverter box cover.
Fastening torque: 2.2 - 2.4 Nm
MG.03.F4.02 - VLT is a registered Danfoss trademark
® ® ® ® ®
DriveMotor FCM 300 Quick Setup
DriveMotor FCM 300 Quick Setup
DriveMotor FCM 300 Quick Setup
DriveMotor FCM 300 Quick Setup
DriveMotor FCM 300 Quick Setup
Ambient temperature
To avoid the FC part getting overheated, the
ambient temperature is not to exceed 40 °C
and the 24-hour average temperature is not
(see fig. 2).
3
voltage on the FC motor is dangerous
and may lead to material damage,
serious injury or it may be fatal.
L
and L
:
1,
2
3
Make sure that your mains supply
corresponds to the voltage required by the
FC motor (see inverter label), TT and NT
mains .
and the earth to the separate terminal
3
ques
ques
ques
ques
FCM 305-340
0,5-0,6 Nm
FCM 355-375
1,2-1,5 Nm
3,4 Nm
N N N N N B! B! B! B! B!
You cannot change the rotation direction of
the motor by shifting around the phases. The
direction of rotation is clockwise by default.
T T T T T ools for installation
ools for installation
ools for installation
ools for installation
ools for installation
1 cross-point screwdriver
1 large screwdriver
1 small screwdriver
Min. 2 glands:
Gland sizes
FCM 305-330
FCM 340-375
1 mains cable
1 control cable
Max. cable cross section
Mains supply cable
Control cable
Serial communication cable
NB!
NB!
NB!
NB!
NB!
Bearings
Ball and roller bearings are despatched from the
works fully charged with grease. Shielded bearings
have sufficient grease for an operating life of at least two
years in normal ambient temperatures, providing there is
little or no leakage.
Tapping of fitments onto the motor shaft,
with a hammer or mallet, causes bearing
damage. This results in increased bearing
noise and a significant reduction in bearing
life.
Pr Pr Pr Pr Prefuses Max.
efuses Max.
efuses Max.
efuses Max.
efuses Max.
UL
1)
FCM 305-322
10A
FCM 330-340
15A
FCM 355-375
25A
IEC
1)
FCM 305-375
25A
, L
1
2
1)
Type gG prefuses must be used. If you want to maintain
UL/cUL you must use prefuses of the type Bussmann
KTS-R 500 V or Ferraz Shawmut, type ATMR (max. 30A). The
fuses must be placed for protection in a circuit that is capable of
supplying a maximum of 100,000 amps RMS (symmetrical), 500
V maximum.
Contr
Contr
ol terminals
ol terminals
Contr
Contr
Control terminals
ol terminals
ol terminals
For information on terminal blocks X100 and X101, please
see table A and B.
RS 485 switch
RS 485 switch
RS 485 switch
RS 485 switch
RS 485 switch
For terminating an RS 485 interface serial communication,
the bus must be terminated by a resistor network at both
ends. This is provided by setting both switches to ON.
L
1,
2
LEDs
LEDs
LEDs
LEDs
LEDs
The FC motor has five LEDs which indicate the status of
the FC motor:
LED 300 (red):
LED 301 (yellow):
LED 302 (green):
LED 303-304 (green):
EMC-corr
EMC-correct installation
EMC-corr
ect installation
ect installation
ect installation
EMC-corr
EMC-corr
ect installation
The control cables must be screened cables to ensure
EMC-correct electrical installation.
Connect the screen to earth at both ends.
Avoid installation with twisted screen ends (pigtails), since
this ruins the screening effect at high frequencies. Use
cable clamps instead.
Use the start button to start the FC motor and adjust the
speed by means of the potentiometer.
The voltage on the FC motor is
dangerous when the motor is connected
to mains. Incorrect installation of the FC
motor may lead to material damage or
serious injury or it may be fatal.
175R0129
3X PG16
1X PG21, 2X PG16
4.0 mm
2
/10 AWG
1.5 mm
2
/16 AWG
2
1.5 mm
/16 AWG
Fault trip
Warning
Power on
Communication

Advertisement

loading